Technical Data and Specifications
IEC Contactors and Starters
Frame L–R
Coil Data—Frame L–R
Note
1
Control transformer with U
k
<
6%.
Description XTCE185L
XTCE225L,
XTCE250L
XTCE300M,
XTCE400M XTCE500M
Voltage Tolera nce
Pickup (x U
c
)
XTCE185L–XTCEC20R 0.7 x U
cmin
—1.15 x U
cmax
XTCS185L–XTCS500M 0.85 x U
cmin
1.1 x U
cmax
Dropout (x U
c
)
XTCE185L–XTCEC20R 0.2 x U
cmin
—0.6 x U
cmax
XTCS185L–XTCS500M 0.2 x U
cmin
—0.4 x U
cmax
Power Consumption of the Coil at Cold State and 1.0 x U
c
XTCE185L–XTCEC20R
Pickup VA 250
1
250
1
450
1
450
1
Pickup W 200 200 350 350
Sealing VA 4.3 4.3 4.3 4.3
Sealing W 3.3 3.3 3.3 3.3
XTCS185L–XTCS500M
Pickup VA 360 360 715 715
Pickup W 325 325 645 645
Sealing VA 4.3 4.3 4.3 4.3
Sealing W 3.3 3.3 3.3 3.3
Duty Factor (%DF) 100 100 100 100
Switching Time at 100% Main Contact U
c
(Approximate Values)
XTCE185L–XTCEC20R
Closing delay (ms)
Opening delay (ms) <100 <100 <80 <80
XTCS185L–XTCS500M <80 <80 <80 <80
Closing delay (ms) <50 <50 <50 <50
Opening delay (ms) <40 <40 <40 <40
Reaction in Threshold and Sealing State Transition Range (XTCE185L–XTCEC20R)
Voltage interruptions
(0–0.2 x U
cmin
)
<
10 ms Time is bridged successfully
(0–0.2 x U
cmin
) >10 ms Dropout of the contactor
Voltage dips
(0.2–0.6 x U
cmin
)
<
12 ms Time is bridged successfully
(0.2–0.6 x U
cmin
) >12 ms Dropout of the contactor
(0.6–0.7 x U
cmin
) Contactor remains switched on
Excess voltage
(1.15–1.3 x U
cmax
) Contactor remains switched on
(>1.3 x U
cmax
)
<
3s Contactor remains switched on
(>1.3 x U
cmax
) >3s Dropout of the contactor
Pickup phase
(0–0.7 x U
cmin
) Contactor does not switch on
(0.7 x U
cmin
–1.15 x U
cmax
) Contactor switches on with certainty
(>1.15 x U
cmax
) Contactor switches on with certainty
Permissible contact resistance (of the external
command device with actuation of A11), ohms
<
500
<
500
<
500
<
500
Permissible residual current (with actuation
of A11 by the electronics with 0 signal)
<
1
<
1
<
1
<
1
SPS signal level (A3–A4) to IEC/EN 61131-2 (Type 2)
High 15V 15V 15V 15V
Low 5V5V5V5V
Electromagnetic compatibility (EMC) This product is designed for operation in industrial environments. Usage in domestic
areas can cause radio frequency interference (RFI). Noise suppression measures
must be provided for the additional interference.