Technical Data and Specifications
IEC Contactors and Starters
AC Ratings—AC-3 Operation
AC Ratings—AC-4 Operation
Note
1
At maximum permissible ambient temperature.
Description XTCE185L XTCE225L XTCE250L XTCE300M XTCE400M XTCE500M XTCE570M XTCE580N
Rated operational current, 50/60 Hz
1
(I
e
) in amperes
220/230V 185 225 250 300 400 500 580 580
240V 185 225 250 300 400 500 580 580
380/400V 185 225 250 300 400 500 580 580
415V 185 225 250 300 400 500 580 580
440V 185 225 250 300 400 500 580 580
500V 185 225 250 300 400 500 580 580
660/690V 185 225 250 300 400 500 580 580
1000V 76 76 76 95 95 95 95 435
Rated power (P) in kilowatts
220/230V 55 70 75 90 125 155 185 185
240V 62 75 85 100 132 170 200 200
380/400V 90 110 132 160 200 250 315 315
415V 110 132 148 180 240 300 348 348
440V 115 142 157 190 255 345 370 370
500V 132 160 180 21 290 360 420 420
660/690V 175 215 240 286 344 344 344 560
1000V 108 108 108 132 132 132 132 600
Description XTCE185L XTCE225L XTCE250L XTCE300M XTCE400M XTCE500M XTCE570M XTCE580N
Rated operational current, 50/60 Hz
1
(I
e
) in amperes
220/230V 136 164 200 240 296 360 360 456
240V 136 164 200 240 296 360 360 456
380/400V 136 164 200 240 296 360 360 456
415V 136 164 200 240 296 360 360 456
440V 136 164 200 240 296 360 360 456
500V 136 164 200 240 296 360 360 456
660/690V 136 164 200 240 296 360 360 456
1000V 76 76 76 95 95 95 95 348
Rated power (P) in kilowatts
220/230V 41 51 62 75 92 112 112 143
240V 45 54 68 82 101 122 122 156
380/400V 75 90 110 132 160 200 200 250
415V 80 96 117 142 176 216 216 274
440V 85 102 125 151 186 229 229 290
500V 96 116 143 172 214 260 260 330
660/690V 127 155 189 229 283 344 344 440
1000V 108 108 108 132 132 132 132 509