Technical Data and Specifications
IEC Contactors and Starters
AC Ratings—AC-6A Operation
AC Ratings—AC-6B Operation
AC Ratings—AC-1 Operation
Notes
1
Example—The transformer has a nominal current of 10A with an inrush current of 18 times the nominal current. So, the contactor must have an
AC-3 current of 18/6 x 10A = 30A. Using an XTCE032C (32A AC-3) contactor is recommended.
2
Up to 690V.
Description XTCE185L XTCE225L XTCE250L XTCE300M XTCE400M XTCE500M XTCE570M XTCE580N
Transformer loads Values are
application
specific
Values are
application
specific
Values are
application
specific
Values are
application
specific
Values are
application
specific
Values are
application
specific
Values are
application
specific
Values are
application
specific
Calculation is I
e
AC-3 = X / 6 * I
e
transformer where X is the inrush current of the transformer and I
e
transformer is the nominal current.
1
Description XTCE185L XTCE225L XTCE250L XTCE300M XTCE400M XTCE500M XTCE570M XTCE580N
Capacitor loads
Individual compensation rated operational
current I
e
of three-phase capacitors in amperes
Up to 525V 220 220 220 307 307 307 307 463
690V 133 133 133 177 177 177 177 265
Maximum inrush current peak (x I
e
) 3030303030303030
Component lifesaving (operations) 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000
Maximum operating frequency (ops/hr) 200 200 200 200 200 200 200 200
Description XTCE650N XTCE750N XTCE820N XTCEC10N XTCEC14P XTCEC16R XTCEC20R
Conventional free air thermal current, three-pole,
50–60 Hz
at 40°C (I
th
) 1041 1102 1225 1225 1714
2
2200 2450
2
at 50°C (I
th
) 931 986 1095 1095 1533
2
1970 2190
2
at 55°C (I
th
) 888 940 1044 1044 1462
2
1800 2089
2
at 60°C (I
th
) 850 900 1000 1000 1400
2
1800 2000
2
Conventional free air thermal current,
single-pole (I
th
)
2125 2250 2500 2500 3500 4500 5000