Technical Data and Specifications
Reduced Voltage Starters
S611 Solid-State Soft Starters
Technical Data and Specifications
Soft Starters—S611
Description
S611 Soft Starter (Partial Catalog Number)
S611A052 S611A065 S611A072 S611B099
Max. current capacity A 52 65 77 99
FLA range A 26–52 32.5–65 38.5–77 48–99
Dimensions
Width inch (mm) 11.58 (294) 11.58 (294) 11.58 (294) 11.58 (294)
Height inch (mm) 19.45 (494) 19.45 (494) 19.45 (494) 19.45 (494)
Depth inch (mm) 7.46 (189) 7.46 (189) 7.46 (189) 7.46 (189)
Weight lb (kg) 24 (11) 24 (11) 24 (11) 24 (11)
General Information
Bypass mechanical lifespan 10M 10M 10M 10M
Insulating voltage V 660 660 660 660
Ramp time range Seconds 0.5–180 0.5–180 0.5–180 0.5–180
Vibration resistance—non-operating g 3g up to 242A units, 2g on
302A to 414A units
3g up to 242A units, 2g on
302A to 414A units
3g up to 242A units, 2g on
302A to 414A units
3g up to 242A units, 2g on
302A to 414A units
Vibration resistanceoperatingg1111
Shock resistance g 15g up to 242A units, 5g on
302A to 414A units
15g up to 242A units, 5g on
302A to 414A units
15g up to 242A units, 5g on
302A to 414A units
15g up to 242A units, 5g on
302A to 414A units
Electrical Information
Operating voltage V 130–600 130–600 130–600 130–600
Operating frequency Hertz 47–63 47–63 47–63 47–63
Overload setting (frame) % FLA 50–100 50–100 50–100 50–100
Trip class 5, 10, 20, 30 5, 10, 20, 30 5, 10, 20, 30 5, 10, 20, 30
Cabling Capacity (IEC 947)
Number of conductors 1111
Wire sizes AWG 14–2/0 14–2/0 14–2/0 14–2/0
Type of connectors Lug Lug Lug Lug
Control Wiring
Wire sizes AWG 22–12 22–12 22–12 22–12
Number of conductors 2 (or one 12–14 AWG) 2 (or one 12–14 AWG) 2 (or one 12–14 AWG) 2 (or one 12–14 AWG)
Torque requirements lb-in 3.5 3.5 3.5 3.5
Maximum size AWG12121212
Control Power Requirements
Voltage range (120V ±10%) V 108–132 108–132 108–132 108–132
Steady state current A 0.375 0.375 0.375 0.375
Inrush current A 0.5 0.5 0.5 0.5
Ripple %1111
Relays (1) Class A and C
Voltage AC—maximum V 120 120 120 120
Voltage DC—maximum V 24 24 24 24
AmpsmaximumA3333
Environment
Temperature—operating °C –20° to 50°C –20° to 50°C –20° to 50°C –20° to 50°C
Temperature—storage °C –40° to 85°C –40° to 85°C –40° to 85°C –40° to 85°C
Altitude Meters <2000m, derate 0.5% per
100m >2000m
<2000m, derate 0.5% per
100m >2000m
<2000m, derate 0.5% per
100m >2000m
<2000m, derate 0.5% per
100m >2000m
Humidity % <95% non-condensing <95% non-condensing <95% non-condensing <95% non-condensing
Operating position Vertical, line side up Vertical, line side up Vertical, line side up Vertical, line side up
Pollution degree IEC947-1 3333
Impulse withstand voltage IEC947-4-1 V 6000 6000 6000 6000