Cut Sheet

V10-T17-16 Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17.3
Technical Data and Specifications
IEC Contactors and Starters
Coil Data—Frame L–R, continued
Note
1
Control transformer with U
k
<
7%.
Description XTCE580N
XTCE750N,
XTCE820N XTCEC10N XTCEC14P XTCEC20R
Voltage Tolera nce
Pickup (x U
c
)
XTCE185L–XTCEC20R 0.7 x U
cmin
—1.15 x U
cmax
XTCS185L–XTCS500M 0.85 x U
cmin
1.1 x U
cmax
Dropout (x U
c
)
XTCE185L–XTCEC20R 0.2 x U
cmin
—0.6 x U
cmax
XTCS185L–XTCS500M 0.2 x U
cmin
—0.4 x U
cmax
Power Consumption of the Coil at Cold State and 1.0 x U
c
XTCE185L–XTCEC20R
Pickup VA 800
1
800
1
800
1
800
1
1600
1
Pickup W 700 700 700 700 1400
Sealing VA 7.5 7.5 7.5 7.5 7.5
Sealing W 6.5 6.5 6.5 6.5 6.5
XTCS185L–XTCS500M
Pickup VA —————
Pickup W —————
Sealing VA —————
Sealing W —————
Duty Factor (%DF) 100 100 100 100 100
Switching Time at 100% Main Contact U
c
(Approximate Values)
XTCE185L–XTCEC20R
Closing delay (ms) <70 <70 <70 <70 <70
Opening delay (ms) <70 <70 <70 <70 <70
XTCS185L–XTCS500M
Closing delay (ms) —————
Opening delay (ms) —————
Reaction in Threshold and Sealing State Transition Range (XTCE185L–XTCEC20R)
Voltage interruptions
(0–0.2 x U
cmin
)
<
10 ms Time is bridged successfully
(0–0.2 x U
cmin
) >10 ms Dropout of the contactor
Voltage dips
(0.2–0.6 x U
cmin
)
<
12 ms Time is bridged successfully
(0.6–0.7 x U
cmin
) Dropout of the contactor
(0.6–0.7 x U
cmin
) Contactor remains switched on
Excess voltage
(1.15–1.3 x U
cmax
) Contactor remains switched on
(>1.3 x U
cmax
)
<
3s Contactor remains switched on
(>1.3 x U
cmax
) >3s Dropout of the contactor
Pickup phase
(0–0.7 x U
cmin
) Contactor does not switch on
(0.7 x U
cmin
–1.15 x U
cmax
) Contactor switches on with certainty
(>1.15 x U
cmax
) Contactor switches on with certainty
Permissible contact resistance (of the external
command device with actuation of A11), ohms
<
500
<
500
<
500
<
500
<
500
Permissible residual current (with actuation
of A11 by the electronics with 0 signal)
<
1
<
1
<
1
<
1
<
1
SPS signal level (A3–A4) to IEC/EN 61131-2 (Type 2)
High 15V 15V 15V 15V 15V
Low 5V5V5V5V5V
Electromagnetic compatibility (EMC) This product is designed for operation in industrial environments. Usage in domestic areas can cause radio frequency interference (RFI).
Noise suppression measures must be provided for the additional interference.