Cut Sheet

V10-T17-28 Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17.3
Technical Data and Specifications
IEC Contactors and Starters
AC Ratings—AC-6A Operation
AC Ratings—AC-6B Operation
AC Ratings—Four-Pole—AC-1 Operation
AC Ratings—Four-Pole—AC-3 Operation
Note
1
Example—The transformer has a nominal current of 10A with an inrush current of 18 times the nominal current. So, the contactor must have an
AC-3 current of 18/6 x 10A = 30A. Using an XTCE032C (32A AC-3) contactor is recommended.
Description XTCE650N XTCE750N XTCE820N XTCEC10N XTCEC14P XTCEC16R XTCEC20R
Transformer loads Values are
application
specific
Values are
application
specific
Values are
application
specific
Values are
application
specific
Values are
application
specific
Values are
application
specific
Values are
application
specific
Calculation is I
e
AC-3 = X / 6 * I
e
transformer where X is the inrush current of the transformer and I
e
transformer is the nominal current.
1
Description XTCE650N XTCE750N XTCE820N XTCEC10N XTCEC14P XTCEC16R XTCEC20R
Capacitor loads
Individual compensation rated operational
current I
e
of three-phase capacitors in amperes
Up to 525V 463 463 463 463
690V 265 265 265 265 — — —
Maximum inrush current peak (x I
e
) 30303030—
Component lifesaving (operations) 100,000 100,000 100,000 100,000
Maximum operating frequency (ops/hr) 200 200 200 200
Description XTCF020B XTCF032C XTCF045C XTCF063D XTCF080D XTCF125G XTCF160G XTCF200G
Conventional free air thermal current, three-pole, 50-60 Hz
Open (amps)
at 40°C (I
th
) 22 32 45 3 80 125 160 200
at 50°C (I
th
) 213041607611615188
at 60°C (I
th
) 2028395469108138172
Enclosed (amps) 18 27 36 50 64 100 128 160
Conventional free air thermal current, single-pole
Open (amps) 60 84 117 162 207 325 415 516
Enclosed (amps) 54 76 105 146 186 292 373 464
Description XTCF020B XTCF032C XTCF045C XTCF063D XTCF080D XTCF125G XTCF160G XTCF200G
Rated operational current, 50/60 Hz (I
e
) in amperes
220/230V 12 18 25 40 50 80 95 115
240V 12 18 25 40 50 80 95 115
380/400V 12 18 25 40 50 80 95 115
415V 12 18 25 40 50 80 95 115
440V 12 18 25 40 50 80 95 115
500V 10 18 25 40 50 80 95 115
660/690V 7 12152532658093
Rated power, (P) in kilowatts
220/230V 3.5 5 7.5 2.5 15.5 25 30 37
240V 4 5.5 8.5 13.5 17 27.5 33 40
380/400V 5.5 7.5 11 18.5 22 37 45 55
415V 7 1014.52430485770
440V 7.510.515.52532516075
500V 47 12 17.5 28 36 58 70 85
660/690V 6.511142330637590