17.3
Technical Data and Specifications
IEC Contactors and Starters
Switching Duty for Non-Motor Loads, Three-Pole,
Four-Pole—XTCE185L–XTCEC14P Short-Time Loading, Three-Pole—XTCE185L–XTCEC20R
Maximum Operating Frequency—Related to Rating and Utilization Category (400V)
Note
1
P
N
= maximum motor rating (kW/hp) of the relevant contactor.
ops/hr = maximum number of operations per hour.
AC-1/400V
Breaking Current A
Component Lifespan (Millions of operations)
0.1 0.2 0.5 70.7 13510
2
1
3
4
0.3 2
5
900
850
1400
1000
700
800
500
400
275
300
350
160
100
55
35
20
10
7
XTCE185L
XTCE225L
XTCE400M
XTCE300M
XTCE250M
XTCE750N
XTCE650N
XTCE500M
XTCE580N
XTCEC14P
XTCE820N/XTCEC10N
10
Min
15
Min
1
Min
3
Min
5
Min
Seconds
AC-1/400V
A
Short-Time Current
Duration of Load
XTCEC10N, XTCEC14P, XTCEC20R
900
30070 1005020 30357102
8000
10000
6000
5000
4000
3000
2500
2000
1000
700
500
400
300
1500
XTCE185L/XTCE225L
XTCE250M
XTCE300M
XTCE400M
XTCE500M
700200 500
200
XTCE580N
XTCE650N
XTCE750N
XTCE820N
6000
4000
2000
1000
800
600
400
200
100
0
10
20 30 40
50
60
70
80 90
100 %
P
N
(kW/hp)
1
2
5
3
4
Ops/hr
Utilization Category
1
Characteristic Curve Above
Type AC-1 AC-3
AC-2
AC-4
XTCE007B–XTCE015B 3 1 5
XTCE018C–XTCE032C 3 2 5
XTCE040D–XTCE065D 3 2 5
XTCE080F–XTCE150G 3 4 5
P
N
(kW/hp)
Ops/hr
4000
3000
2000
600
500
400
300
200
150
100
50
0
10
20 30 40
50
60
70
80 90
100 %
1500
1000
800
a
b
d
c
e
f
g
Utilization Category
1
Typ e
Characteristic Curve
Above
Typ e
Characteristic Curve
Above
AC-1 AC-3 AC-4 AC-1 AC-3 AC-4
XTCE185L 2 1 6 XTCE500M 3 2 7
XTCE225L 2 1 6 XTCE580N 3 4 5
XTCE250L 2 1 6 XTCE650N 3 4 5
XTCE300M 3 2 7 XTCE750N 3 4 5
XTCE400M 3 2 7 XTCE820N 3 4 5
7–150 hp
185–820 hp