17.8
Technical Data and Specifications
Control Power Transformer Selection
Component VA Table
Note
1
Intermittent duty coil.
Inrush Sealed
VAR Watts VA VAR Watts VA
Relays
Type AA (single- and two-pole) 18 8.5 20 8 6.6 11
Type D15 6449807.12.47.5
Type M (two- to 12-pole) 122 95 155 20 9 22
Type M latch coil 36.5 18.5 41 13 11 17
Type MRD 168 13.2 13.2
Type MRD latch coil
1
—21.6——21.6
Type R 66—66
Type RM
Set ————3.53.5
Release ————3.13.1
Type TF 334334
Type TH 445445
Timers
Type D80 606790186 19
Type D80 with inst. contacts 89 95 130 20 7 21
Freedom Series Starters and Contactors
IEC
Frames A–C 64 49 80 7.1 2.4 7.5
Frames D–F 78 65 100 9.2 3.1 10
Frames G–K 210 95 230 27 7.8 28
Frames L–N 374 112 390 48 13 49.8
Frames P–S 1132 216 1040 96 17 116
Frames T–U 798 950 10 11
Frame V 1345 1600 22 25
Frames WX ——1000——23
Frame Z ——2400——70
NEMA
Size 00 64 49 80 7.1 2.4 7.5
Size 0 78651009.23.110
Sizes 1–2 210 95 230 27 7.8 28
Size 3 374 112 390 48 13 49.8
Sizes 4–5 1132 240 1158 96 27.2 100
Sizes 6–7 868 1345 1600 11 22 25
Size 8 2060 2450 60 75