6.1
Pump Panels
Industrial Pump Panels
A200—Fusible Disconnect
Product Description
Three-phase magnetic
Interchangeable heater
OLR
Standard ECN54 controllers
have a HAND/OFF/AUTO
selector switch and START
and RESET pushbuttons
mounted on the enclosure
and are wired as illustrated on
Page V10-T6-12.
Type 3R enclosure does not
include top conduit hubs.
Hubs are available in kit
form—see table on Page
V10-T6-5.
If branch circuit protective
device is 45A or greater,
C320FBR1 fuse kit (panel
mounted) may be required for
control circuit protection per
NEC 430-72.
Stainless steel enclosure may
be ordered by changing the
seventh digit to
A. Type 3R
rating will still apply.
Product Selection
Class EC254—Combination A200 Pump Panel—Fusible Disconnect
Notes
Starters do not include heater packs. Select 1 carton of 3 heater packs. For heater pack selection, see Tab 15.
1
Dual element fuse ratings.
2
Class R fuse clips, except for Size 7 which uses Class L fuse clips. For starters with clips “Not Installed”, select fuse clip kit on Page V10-T6-8.
3
To order without the START pushbutton, add modification code P6.
NEMA
Size
Motor
Voltage
1
Max. hp
50/60 Hz
Fuse Clip Rating
2
Narrow Width
3
Standard Width
3
Amperes Volts Catalog Number Catalog Number
1 230 7-1/2 30 250 EC25412BAB-E14 EC25412BAB
460 10 600 EC25412CAC-E14 EC25412CAC
Not installed Not installed EC25412AAA-E14 EC25412AAA
2 230 15 60 250 EC25422BAD-E14 EC25422BAD
460 25 600 EC25422CAE-E14 EC25422CAE
Not installed Not installed EC25422AAA-E14 EC25422AAA
3 230 30 100 250 EC25432BAF
460 50 600 EC25432CAG
Not installed Not installed EC25432AAA
4 230 50 200 250 EC25442BAH
460 100 600 EC25442CAJ
Not installed Not installed EC25442AAA
5 230 100 400 250 EC25452BAK
460 200 600 EC25452CAL
6 230 200 600 250 EC25462BAM
460 400 600 EC25462CAN
7 460 600 1200 600 EC25472CAQ
For Other Volts and Hertz
Applications
For other than listed volts and
hertz, select required
controller by catalog number
and replace the magnet coil
alpha designation, eighth digit
in catalog number, with
proper code suffix from the
table below.
Example: For 600V 60 Hz coil,
change EC25412BAC to
EC25412DAC.
Coil Voltage
Coil Volts and Hertz Suffix Code
120/60 or 110/50 A
240/60 or 220/50 B
480/60 or 440/50 C
600/60 or 550/50 D
208/60 E