6.1
Pump Panels
Industrial Pump Panels
A200—Circuit Breaker
Product Description
Three-phase magnetic
Interchangeable heater
OLR
These ECN55 pump controllers
feature the A200 starters.
They have a HAND/OFF/
AUTO selector switch and
START pushbutton mounted
on the enclosure and a
RESET button on the front—
wiring is as illustrated in
the wiring diagram on Page
V10-T6-12.
Type 3R enclosure does not
include top conduit hubs.
Hubs are available in kit
form—see Page V10-T6-5.
If branch circuit protective
device is 45A or greater,
C320FBR1 fuse kit (panel
mounted) may be required for
control circuit protection per
NEC 430-72.
Stainless steel enclosure may
be ordered by changing the
seventh digit to
A. Type 3R
rating will still apply.
Product Selection
Class EC255—Combination A200 Pump Panel—Circuit Breaker
Notes
Starters do not include heater packs. Select one carton of three heater packs. For heater pack selection, see Tab 15.
1
To order without the START pushbutton, add modification code P6.
2
Consult factory in the event ground fault protection is required.
3
Supply hp, voltage, FLA and whether motor is design E or not when ordering the starter.
NEMA
Size
Motor
Voltage
Max. hp
50/60 Hz
Circuit Breaker
Size
Narrow Width
1
Standard Width
2
Catalog
Number
Catalog
Number
123017A EC25512BAC-E14 EC25512BAC
315A EC25512BAD-E14 EC25512BAD
7-1/2 30A EC25512BAE-E14 EC25512BAE
460 1 3A EC25512CAB-E14 EC25512CAB
37A EC25512CAC-E14 EC25512CAC
515A EC25512CAD-E14 EC25512CAD
10 30A EC25512CAE-E14 EC25512CAE
2 230 10 50A EC25522BAF-E14 EC25522BAF
460 25 EC25522CAF-E14 EC25522CAF
3 230 30 100A EC25532BAG
460 50 EC25532CAG
4 230 50 150A EC25542BAH
460 100 EC25542CAH
5 230 60 250A EC25552BAJ
100 400A EC25552BAK
460 150 250A EC25552CAJ
200 400A EC25552CAK
6 230 125 600A EC25562BAL
200 800A EC25562BAM
460 300 600A EC25562CAL
400 800A EC25562CAM
7
2
230 250
3
EC25572BAU
300 EC25572BAU
460 500 EC25572CAU
600 EC25572CAU
For Other Volts and Hertz
Applications
For other than listed volts and
hertz, select required
controller by catalog number
and replace the magnet coil
alpha designation, eighth digit
in catalog number with proper
code suffix from the table
below.
Example: For 600V 60 Hz coil,
change EC25512CAC to
EC25512DAC.
Coil Voltage
Coil Volts and Hertz Suffix Code
120/60 or 110/50 A
240/60 or 220/50 B
480/60 or 440/50 C
600/60 or 550/50 D
208/60 E