Heater Selection—Starter Size 3 and 4
Heater Selection—Starter Size 4
Note
1
Ambient compensated.
Motor Full Load
Current in Amperes
1
Style
Number
Maximum
Breaker or Fuse Catalog Number
19.0–20.8 179C319G02 80 FH72
20.9–22.9 179C319G03 90 FH73
23.0–25.2 179C319G04 100 FH74
26.3–27.8 179C319G05 100 FH75
27.9–30.6 179C319G06 110 FH76
30.7–33.5 179C319G07 125 FH77
33.6–37.5 179C319G08 150 FH78
37.6–41.5 179C319G09 150 FH79
41.6–46.3 179C319G10 175 FH80
46.4–50.0 179C319G11 200 FH81
51.0–55.0 179C319G12 200 FH82
56.0–61.0 179C319G13 225 FH83
62.0–66.0 179C319G14 250 FH84
67.0–73.0 179C319G15 250 FH85
74.0–79.0 179C319G16 250 FH86
80.0–87.0 179C319G17 300 FH87
88.0–90.0 179C319G18 350 FH88
Motor Full Load
Current in Amperes
1
Style
Number
Maximum
Breaker or Fuse Catalog Number
88.0–95.0 179C319G18 350 FH88
96.0–105.0 179C319G19 300 FH89
106.0–116.0 179C319G20 300 FH90
117.0–128.0 179C319G21 350 FH91