Technical Data and Specifications
IEC Contactors and Starters
Auxiliary Contacts
Auxiliary Contacts Technical Data and Specifications
Notes
1
Making and breaking conditions to DC-13, time L/R contact as stated.
2
Conventional thermal current (I
th
) of XTCEXSCC_ is 10A.
3
See fuses overlay for time/current characteristic (on request).
Description
XTCE007B_–
XTCE032C
XTCEXFAC_
XTCEXFATC_
XTCEXFCC_
XTCEXSCC_ XTCEXFAG_
XTCEXSBLN_
XTCEXSBN_
XTCEXSBNC_
XTCEXSCN_
XTCEXSCNC_
Interlocked opposing contacts with an auxiliary contact
module (to IEC 60947-5 -1 Annex L)
Yes Yes Yes Yes
Break contact (not late-break contact) suitable as a mirror
contact (to IEC/EN 60947-4 -1 Annex F)
XTCE007B_–
XTCE032C
XTCE007B_–
XTCE032C
XTCE007B_–
XTCE032C
XTCE040D_–
XTCE065D_
XTCE040D_–
XTCE065D_
XTCE185L_–
XTCEC10N_
Rated impulse withstand voltage, (U
imp
) Vac 6000 6000 6000 6000 6000
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3
Rated insulation voltage, (U
i
) Vac 690 690 690 690 690
Rated operational voltage, (U
e
) Vac 500 500 500 500 500
Safe isolation to VDE 0106 Part 101 and Part 101(A) in Vac
Between coil and auxiliary contacts 400 400 400 440 440
Between the auxiliary contacts 400 400 400 440 440
Rated operational current, l
e
AC-15
230V 6A 6A 6A 6A 6A
380/415V 4A 3A 4A 4A 4A
500V 1.5A 1.5A 1.5A 1.5A
DC-3 L/R
<
5 ms
1
24V 10A 10A 10A 10A 10A
60V 6A 6A 6A 6A 6A
110V 3A 3A 3A 3A 3A
220V 1A 1A 1A 1A 1A
Conventional thermal current, I
th
16A 16A 16A
2
10A 10A
Control circuit reliability
(at U
e
= 24 Vdc, U
min
= 17 V, I
min
= 5.4 mA)
<10
-8
, < one failure at 100 million operations
Component lifespan, operations x 10
6
at
U
e
= 230V, AC-15, 3A 1.3 1.3 1.3 1.3 1.3
Short-circuit rating without welding
3
Maximum fuse, gG/gL 10A 10A 10A 16A 16A