Technical Data and Specifications
IEC Contactors and Starters
AC Ratings—AC-3 Operation
AC Ratings—AC-4 Operation
Note
1
At maximum permissible ambient temperature.
Description XTCE650N XTCE750N XTCE820N XTCEC10N XTCEC14P XTCEC16R XTCEC20R
Rated operational current, 50/60 Hz
1
(I
e
) in amperes
220/230V 650 750 820 1000 — 1600
240V 650 750 820 1000 — 1600
380/400V 650 750 820 1000 — 1600
415V 650 750 820 1000 — 1600
440V 650 750 820 1000 — 1600
500V 650 750 820 1000 — 1600
660/690V 650 750 820 1000 — 1600
1000V 435 580 580 700 — —
Rated power (P) in kilowatts
220/230V 205 240 260 315 500
240V 225 260 285 340 — 550
380/400V 355 400 450 560 900
415V 390 455 500 610 — 930
440V 420 480 525 650 1000
500V 470 550 600 730 — 1180
660/690V 630 720 750 1000 — 1600
1000V 600 800 800 1000 — —
Description XTCE650N XTCE750N XTCE820N XTCEC10N XTCEC14P XTCEC16R XTCEC20R
Rated operational current, 50/60 Hz
1
(I
e
) in amperes
220/230V 512 576 656 800 — 1280
240V 512 576 656 800 — 1280
380/400V 512 576 656 800 — 1280
415V 512 576 656 800 — 1280
440V 512 576 656 800 — 1280
500V 512 576 656 800 — 1280
660/690V 512 576 656 800 — 1280
1000V 348 464 464 700 — —
Rated power (P) in kilowatts
220/230V 161 181 209 260 — 30
240V 176 200 228 280 — 450
380/400V 280 315 355 450 750
415V 307 346 394 490 — 770
440V 32 367 41 520 — 830
500V 370 417 474 590 — 940
660/690V 494 556 633 780 — 1300
1000V 509 678 678 1000 — — —