Cut Sheet

V10-T17-34 Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17.3
Technical Data and Specifications
IEC Contactors and Starters
XTOB Overload Relay—Technical Data and Specifications, continued
Note
1
Rated operational current: Making and breaking conditions to DC-13, L/R constant as stated.
Description
XTOB…BC1,
XTOB…CC1 XTOB…DC1
XTOB…GC1,
XTOB…GC1S XTOB...LC1
Auxiliary and Control Circuit Connections
Impulse withstand voltage (U
imp
) Vac 6000 6000 6000 6000
Overvoltage category/pollution degree III/3 III/3 III/3 III/3
Terminal capacity
Solid, mm
2
2 x (0.75–4) 2 x (0.75–4) 2 x (0.75–4) 2 x (0.75–4)
Flexible with ferrule, mm
2
2 x (0.75–2.5) 2 x (0.75–2.5) 2 x (0.75–2.5) 2 x (0.75–2.5)
Solid or stranded (AWG) 2 x (18–12) 2 x (18–12) 2 x (18–12) 2 x (18–12)
Terminal screw M3.5 M3.5 M3.5 M3.5
Tightening torque
Nm 0.8–1.2 0.8–1.2 0.8–1.2 0.8–1.2
Lb-in 7–10.6 7–10.6 7–10.6 7–10.6
Tools
Pozidriv screwdriver Size 2 Size 2 Size 2 Size 2
Standard screwdriver 1 x 6 1 x 6 1 x 6 1 x 6
Rated insulated voltage (U
i
) Vac 500 500 500 500
Rated operational voltage 500 500 500 500
Safe Isolation to VDE 0106 Part 101 and Part 101/A1
between auxiliary contacts 240 240 240 240
Conventional thermal current, I
th
666
Rated operational current—AC-15
Make contact
120V 1.5 1.5 1.5 1.5
240V 1.5 1.5 1.5 1.5
415V 0.5 0.5 0.5 0.5
500V 0.5 0.5 0.5 0.5
Break contact
120V 1.5 1.5 1.5 1.5
240V 1.5 1.5 1.5 1.5
415V 0.9 0.9 0.9 0.9
500V 0.8 0.8 0.8 0.8
Rated operational current—DC-13 L/R
<
15 ms
1
24V 0.9 0.9 0.9 0.9
60V 0.75 0.75 0.75 0.75
110V 0.4 0.4 0.4 0.4
220V 0.2 0.2 0.2 0.2
Short-circuit rating without welding
Maximum fuse, A gG/gL 6 6 6 6