Cut Sheet

V10-T17-46 Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17.6
Technical Data and Specifications
Reduced Voltage Starters
Kick Start
Selectable feature in both
Voltage Ramp Start and
Current Limit Start modes.
Provides a current and torque
“kick” for 0 to 2.0 seconds.
This provides greater initial
current to develop additional
torque to breakaway a high
friction load.
0–85% of locked rotor
torque
0–2.0 seconds duration
Starting Characteristics—Kick Start
Soft Stop
Allows for a controlled
stopping of a load. Used
when a stop-time that is
greater than the coast-to-stop
time is desired. Often used
with high friction loads where
a sudden stop may cause
system or load damage.
Stop time = 0–60 seconds
Starting Characteristics—Soft Stop
100%
Locked Rotor Torque
Ramp
Time (Seconds)
Kick
Start
Run
Soft
Stop Time
100%
Run Soft Stop
Speed
Time (Seconds)
Coast to Stop
(Speed)
Soft Stop Ramp