17.3
Technical Data and Specifications
IEC Contactors and Starters
AC Ratings—AC-3 Operation
AC Ratings—AC-4 Operation
Note
1
At maximum permissible ambient temperature.
Description XTCE040D XTCE050D XTCE065D XTCE072D XTCE080F XTCE095F XTCE115G XTCE150G XTCE170G
Rated operational current, 50/60 Hz
1
(I
e
) in amperes
220/230V 40 50 65 72 80 95 115 150 170
240V 40 50 65 72 80 95 115 150 170
380/400V 40 50 65 7 80 95 115 150 170
415V 40 50 65 72 80 95 115 150 170
440V 40 50 65 72 80 95 115 15 170
500V 40 50 65 72 80 95 115 150 170
660/690 25 32 37 37 65 80 93 100 150
1000V — — — — —
Rated power (P) in kilowatts
220/230V 12.5 15.5 20 22 25 30 37 48 52
240V 13.5 17 22 35 27.5 34 40 52 57
380/400V 18.5 22 30 37 37 45 55 75 90
415V 24 30 39 41 43 57 70 91 100
440V 25 32 41 44 51 60 75 95 105
500V 28 36 47 45 58 70 85 110 120
660/690V 23 30 35 35 63 75 90 96 140
1000V — — — — —
Description XTCE040D XTCE050D XTCE065D XTCE072D XTCE080F XTCE095F XTCE115G XTCE150G XTCE170G
Rated operational current, 50/60 Hz
1
(I
e
) in amperes
220/230V 18 21 25 25 40 50 55 65 65
240V 18 21 25 25 40 50 55 65 65
380/400V 18 21 25 25 40 50 55 65 65
415V 18 21 25 25 40 50 55 65 65
440V 18 21 25 25 40 50 55 65 65
500V 18 21 25 25 40 50 55 65 65
660/690V 14 17 20 20 40 50 45 50 50
1000V — — — — —
Rated power (P) in kilowatts
220/230V 5 6 7 7 12 16 17 20 20
240V 5.5 6.5 7.5 7.5 13 17 19 22 22
380/400V 9 10 12 12 20 26 28 33 33
415V 9.51113132430333939
440V 10 12 14 14 25 32 35 41 41
500V 11 13 16 16 29 36 40 47 47
660/690V 12 14 17 17 26 35 43 48 48
1000V — — — — —