Technical Data and Specifications
Solid State Overload Relay
C440/XTOE
Electronic Overload Relays up to 1500A
Specification
Description 45 mm 55 mm 110 mm
Electrical Ratings Range Range Range
Operating voltage (three-phase) and frequency 690 Vac (60/50 Hz) 690 Vac (60/50 Hz) 690 Vac (60/50 Hz)
FLA Range
0.33–1.65A
1–5A
4–20A
9–45A
20–100A 28–140A (NEMA)
35–175A (IEC)
Use with Contactors
XT IEC frames B, C, D F, G G, H
Freedom NEMA sizes 00, 0, 1, 2 3 4
Tri p C l a s s
10A, 10, 20, 30
Selectable
10A, 10, 20, 30
Selectable
10A, 10, 20, 30
Selectable
Motor Protection
Thermal overload setting 1.05 x FLA: does not trip
1.15 x FLA: overload trip
1.05 x FLA: does not trip
1.15 x FLA: overload trip
1.05 x FLA: does not trip
1.15 x FLA: overload trip
Feature Range Range Range
Phase loss Fixed threshold 50% Fixed threshold 50% Fixed threshold 50%
Phase unbalance (selectable: enable/disable) Fixed threshold 50% Fixed threshold 50% Fixed threshold 50%
Ground fault (selectable: enable/disable) 50% of FLA dial setting
>150% = 2 sec
>250% = 1 sec
50% of FLA dial setting
>150% = 2 sec
>250% = 1 sec
50% of FLA dial setting
>150% = 2 sec
>250% = 1 sec
Reset Manual/automatic Manual/automatic Manual/automatic
Indicators
Trip status Orange flag Orange flag Orange flag
Mode LED One flash: Overload operating properly
Two flashes: Current is above FLA dial
setting—pending trip
One flash: Overload operating properly
Two flashes: Current is above FLA dial
setting—pending trip
One flash: Overload operating properly
Two flashes: Current is above FLA dial
setting—pending trip
Options
Remote reset Yes Yes Yes
Reset bar Yes Yes Yes
Communication expansion module Yes Yes Yes
Communication adapter Yes Yes Yes
Capacity
Load terminals
Terminal capacity 12–10 AWG (4–6 mm
2
)
8–6 AWG (6–16 mm
2
)
6–1 AWG (16–50 mm
2
) 8–4/0 AWG (10–95 mm
2
)
Tightening torque 20–25 lb-in (2.3–2.8 Nm)
25–30 lb-in (2.8–3.4 Nm)
25–30 lb-in (2.8–3.4 Nm) 124 lb-in (14 Nm)
Input, auxiliary contact and remote reset terminals
Terminal capacity 2 x (18–12) AWG 2 x (18–12) AWG 2 x (18–12) AWG
Tightening torque 7–11 lb-in (0.8–1.2 Nm) 7–11 lb-in (0.8–1.2 Nm) 7–11 lb-in (0.8–1.2 Nm)
Voltages
Insulation voltage U
i
(three-phase) 690 Vac 690 Vac 690 Vac
Insulation voltage U
i
(control) 500 Vac 500 Vac 500 Vac
Rated impulse withstand voltage 6000 Vac 6000 Vac 6000 Vac
Overvoltage category/pollution degree III/3 III/3 III/3