Technical Data and Specifications
Reduced Voltage Starters
Soft Starters—S811+, continued
Note
1
UR recognized product.
Description
S811+V50_ S811+V65_ S811+V72_ S811+V85_ S811+V10_
1
Max. current capacity 500 650 720 850 1000
FLA range 156–500 203–650 225–720 265–580 320–1000
General Information
Bypass mechanical lifespan 10M 10M 10M 10M 10M
Insulating voltage Ui 660V 660V 660V 660V 660V
Ramp time range 0.5–180 seconds (0.5–360
seconds S811+ Premium)
0.5–180 seconds (0.5–360
seconds S811+ Premium)
0.5–180 seconds (0.5–360
seconds S811+ Premium)
0.5–180 seconds (0.5–360
seconds S811+ Premium)
0.5–180 seconds (0.5–360
seconds S811+ Premium)
Resistance to vibration3g3g3g3g3g
Resistance to shock 15g 15g 15g 15g 15g
Electrical Information
Operating voltage 200–600V 200–600V 200–600V 200–600V 200–600V
Operating frequency 47–63 Hz 47–63 Hz 47–63 Hz 47–63 Hz 47–63 Hz
Overload setting 30–100% 30–100% 30–100% 30–100% 30–100%
Trip class 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30
Cabling Capacity (IEC 947)
Number of conductors 2, 4 or 6 2, 4 or 6 2, 4 or 6 2, 4 or 6 2, 4 or 6
Wire sizes 2/0 to 500 kcmil 2/0 to 500 kcmil 2/0 to 500 kcmil 2/0 to 500 kcmil 2/0 to 500 kcmil
Type of connectors Add-on lug kit Add-on lug kit Add-on lug kit Add-on lug kit Add-on lug kit
Control Wiring (12-Pin)
Wire sizes in AWG 22–14 22–14 22–14 22–14 22–14
Number of conductors (stranded) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12)
Torque requirements in lb-in 3.5 3.5 3.5 3.5 3.5
Solid, stranded or flexible max. size in mm
2
3.31 3.31 3.31 3.31 3.31
Control Power Requirements
Voltage range (24V ±10%) 21.6–26.4 21.6–26.4 21.6–26.4 21.6–26.4 21.6–26.4
Steady-state current amps 1.4 1.4 1.4 1.4 1.4
Inrush current amps 10 10 10 10 10
Ripple 1% 1% 1% 1% 1%
Relays (1) Class A and C
Voltage AC—maximum 240 240 240 240 240
Voltage DC—maximum 120 120 120 120 120
Ampsmaximum33333
Environment
Temperature—operating –30 to 50°C (no derating)
consult factory for
operation >50°C
–30 to 50°C (no derating)
consult factory for
operation >50°C
–30 to 50°C (no derating)
consult factory for
operation >50°C
–30 to 50°C (no derating)
consult factory for
operation >50°C
–30 to 50°C (no derating)
consult factory for
operation >50°C
Temperature—storage –50 to 70°C –50 to 70°C –50 to 70°C –50 to 70°C –50 to 70°C
Altitude <2000m—consult factory
for operation >2000m
<2000m—consult factory
for operation >2000m
<2000m—consult factory
for operation >2000m
<2000m—consult factory
for operation >2000m
<2000m—consult factory
for operation >2000m
Humidity <95% noncondensing <95% noncondensing <95% noncondensing <95% noncondensing <95% noncondensing
Operating position Any Any Any Any Any
Pollution degree IEC947-133333
Impulse withstand voltage IEC947-4-1 6000V 6000V 6000V 6000V 6000V