Time Current Curves TC01200002E Effective March 2018 Supersedes May 2017 Series C F-frame circuit breaker time current curves Contents Description Page Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents (continued) Two-, three-, and four-pole thermal-magnetic trip units Series Series Series Series Series Series Series Series Series Series Series Series Series Series Series Series Series Series Series Series Series Series C C C C C C C C C C C C C C C C C C C C C C types types types types types types types types types types types types types types types types types types types types types types Page ED, EHD, FDB, FD, FDC, and HFD 15A . . . . . . . . . . . . . . . . . . . .
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 Revision notes NNote: Unless noted below, all curves remain unchanged from their prior revision. Revision Curve number Page Date Changed FDCE, 600V interruption rating from 35 to 25 TC01203015 6 05-24-17 Deleted curves: SC-4146-87B, SC-4147-87B, SC-4148-87B, SC-4149-87B, SC-6970-98, SC-5805-94A, SC-5528-93A, SC-5529-93A, SC-5530-93A, SC-5531-93A, SC-6871-98. Added 7 new curves, combining FDC data with all other frame data.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 Catalog Number Selection This information is presented only as an aid to understanding catalog numbers. It is not to be used to build catalog numbers for circuit breakers or trip units. Table 1.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 LS LSG LSI LSIG Figure 1. Digitrip 310+ Nameplates LI LSI Figure 2. Digitrip 210+ Nameplates EATON www.eaton.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 2 HOURS Current in Multiples of (lr) 10000 9000 8000 7000 .5 .7 1 3 4 7 5 10 20 30 Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current) Series C F-Frame Circuit Breakers Catalog Types: FDE, HFDE, FDCE Circuit breaker time/current curves (phase current) Trip Unit Types: 32 (LSI), 36 (LSIG) FDE 6000 5000 1 HOUR 2 Types FDE, FDCE, HFDE circuit160A, breakers Available Sensors (In): 80A, 225A I r 1.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current) 2 HOURS Current in Multiples of (lr) 10000 9000 8000 7000 .5 .
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 10000 9000 8000 7000 .1 .2 .3 .4 .7 .5 1.0 2.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 10000 Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current) Series C F-frame circuit breakers (100A and 225A) Catalog Types: FDE, HFDE Profiles: J, K, R, S Trip Unit Types: 22 (LSI) Interrupting Rating Long Delay Pickup @ 115%r I ± 5% Breaker Type UL/CSA rms Sym.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 10000 Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current) Series C F-frame circuit breakers (100A and 225A) Catalog Types: FDE, HFDE Profiles: M, N Trip Unit Types: 22 (LSI) Long Delay Pickup @ 115%r I ± 5% Interrupting Rating Breaker Type UL/CSA rms Sym.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current) 10000 Series C F-frame circuit breakers (100A and 225A) Catalog Types: FDE, HFDE Profiles: P, Q Trip Unit Types: 22 (LSI) Interrupting Rating Long Delay Pickup @ 115%r I ± 5% Breaker Type UL/CSA rms Sym.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current) 10000 Series C F-frame circuit breakers (100A and 225A) Catalog Types: FDE, HFDE Profiles: L, O Trip Unit Types: 22 (LSI) Interrupting Rating Long Delay Pickup @ 115%r I ± 5% Breaker Type UL/CSA rms Sym.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current) Series C F-frame circuit breakers (100A and 225A) 10000 Catalog Types: FDE, HFDE Trip Unit Types: 21 (LI) Interrupting Rating Long Delay Pickup @ 115%r I ± 5% Breaker Type UL/CSA rms Sym. kA, 50/60 Hz 240Vac 480Vac 600Vac FDE HFDE 65 100 Setting J K L M N O P Q R S 100 Long Delay @ 6× Ir +0%/-30% 2× 2.5x li(xln) 2 2.5 3 3.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current) 10000 Series C F-frame circuit breakers (225A) Catalog Types: FDE, HFDE Trip Unit Types: 21 (LSI) Interrupting Rating Long Delay Pickup @ 115%r I ± 5% Breaker Type UL/CSA rms Sym.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 300 CURRENT IN AMPERES 15A 2 HOURS 2 HOURS 5 6 7 8 9 10 10,000 5,000 1 HOUR Circuit breaker time/current curves Series C F-frame circuit breakers 3,000 3,000 1 HOUR 5,000 Catalog Types: EHD, FD and HFD circuit breakers, single-pole. 2,000 ambient, 2,000 For application and coordination purposes only.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 2 HOURS 2 HOURS 5 6 7 8 9 10 10,000 300 CURRENT IN AMPERES 20A 5,000 1 HOUR Circuit breaker time/current curves Series C F-frame circuit breakers 3,000 Catalog Types: EHD, FD and HFD circuit breakers, single-pole. 2,000 2,000 cold start. For application and coordination purposes only.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 300 CURRENT IN AMPERES 25A 2 HOURS 2 HOURS 5 6 7 8 9 10 10,000 5,000 1 HOUR Circuit breaker time/current curves Series C F-frame circuit breakers 3,000 Catalog Types: EHD, FD and HFD circuit breakers, single-pole. 3,000 1 HOUR 5,000 2,000 For application and coordination purposes only.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 300 CURRENT IN AMPERES 30A 2 HOURS 2 HOURS 5 6 7 8 9 10 10,000 5,000 1 HOUR Circuit breaker time/current curves Series C F-frame circuit breakers 3,000 Catalog Types: EHD, FD and HFD circuit breakers, single-pole. 3,000 1 HOUR 5,000 2,000 For application and coordination purposes only.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 100 30 2 HOURS 20 Catalog types EHD, FD and HFD circuit breakers, single-pole. 1 HOUR 3,000 Catalog Types: EHD, FD and HFD circuit breakers, single-pole. Maximum Vac : 277 at 50/60 Hz Maximum Vdc : 3,000 125 For application and coordination purposes only. Based on 40°C ambient, 2,000 cold start.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 2 HOURS Circuit breaker time/current curves ® Series C F-frame circuit breakers Catalog types EHD, FD and HFD circuit breakers, single-pole. 5,000 1 HOUR For application and coordination purposes only. Circuit breaker time/current curves Based on 40˚C ambient, cold start.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 2 HOURS 5000 4000 6000 7000 8000 9000 10000 2 HOURS Circuit breaker time/current curves Series C ® F-frame circuit breakers Catalog types EHD, FD and HFD circuit breakers, single-pole. 1 HOUR rated wire (60˚C up to 100A, 75˚C above 125A) per terminal. Series C F-frame circuit breakers Tested in open air. 3,000 Catalog Types: and Maximum Vac EHD, 50/60 HzHFD circuit breakers, single-pole.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 2 HOURS Circuit breaker time/current curves ® Series C F-frame circuit breakers Catalog types EHD, FD and HFD circuit breakers, single-pole. 1 HOUR For application and coordination purposes only. Circuit breaker time/current Based on 40˚C ambient, cold start.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 2 HOURS Circuit breaker time/current curves ® Series C F-frame circuit breakers 1 HOUR 3,000 Catalog Types: FD Maximum Vac: 277 at EHD, 50/60 Hz Maximum Vdc: 125 Breaker rating with four (4) feet of rated wire (60°C Connected Continuous terminal. Tested in openInstantaneous air.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 100 30 2 HOURS 20 Circuit breaker time/current curves Series C ® F-frame circuit breakers Catalog types EHD, FD and HFD circuit breakers, single-pole. 1 HOUR For application and coordination purposes only. Circuit breaker curves Based on 40˚C ambient, time/current cold start.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 2 HOURS Circuit breaker time/current curves Series C ® F-frame circuit breakers 1 HOUR 3,000 Catalog Types: FD Maximum Vac: 277 atEHD, 50/60 Hz Maximum Vdc: 125 Breaker rating with four (4) feet of rated wire (60°C Connected Continuous terminal. Tested in openInstantaneous air.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 100 30 2 HOURS 20 Circuit breaker time/current curves ® Series C F-frame circuit breakers 1 HOUR 3,000 Catalog Types: Maximum Vac: 277 atEHD, 50/60 FD Hz Maximum Vdc: 125 3,000 and HFD circuit breakers, single-pole. For application and coordination purposes only. Based on 40°C 2,000ambient, cold start.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 300 CURRENT IN AMPERES 100A 2 HOURS Circuit breaker time/current curves ® Series C F-frame circuit breakers 1 HOUR 3,000 Catalog EHD,HzFD Maximum Vac:Types: 277 at 50/60 Maximum Vdc: 125 Breaker rating with four (4) feet of rated wire (60°C Connected Continuous terminal. Tested in open air.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 100 30 2 HOURS 20 2 HOURS 5 6 7 8 9 10 10,000 300 CURRENT IN AMPERES 110A ® F-frame circuit breakers Circuit breaker time/current curves 1 HOUR 5,000 Catalog Types: EHD, FD and HFD circuit breakers, single-pole. 1 HOUR Series C F-frame circuit breakers 5,000 3,000 For application and coordination purposes only.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ® 6000 7000 8000 9000 10000 F-frame circuit breakers For application and coordination purposes only. 1 HOUR Circuit breaker time/current curves Based on 40˚C ambient, cold start. Connected with four (4) feet of rated wire (60˚C up to 100A, 75˚C above 125A) per terminal. Series F-frame circuit breakers TestedC in open air. 3,000 Catalog Types: and HFD Maximum Vac: FD 277 at 50/60 Hz circuit breakers, single-pole.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 6000 7000 8000 9000 10000 5000 4000 Circuit breaker time/current curves Series C ® F-frame circuit breakers Catalog types FD and HFD circuit breakers, single-pole. 5,000 1 HOUR For application and time/current coordination purposes only. Circuit breaker curves Based on 40˚C ambient, cold start. Connected with four (4) feet of rated wire (60˚C up to 100A, 75˚C above 125A) per terminal.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EHD, FDB FD, HFD, FDC 15A 2, 3 & 4 pole AB DE-ION Circuit Breakers—two-, three-, and four-poles 10000.00 Circuit Breaker time/current curv es Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EHD, FDB FD, HFD, FDC 20A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature. Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series. Tested in open air.
Series C F-Frame Time Current Curves TC01200002E Effective March 2018 ED, EHD, FDB FD, HFD, FDC 25A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature. Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series. Tested in open air.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EDH, EHD, FDB FD, HFD, FDC 30A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD,FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature. Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series. Tested in open air.
Series C F-Frame Time Current Curves TC01200002E Effective March 2018 ED, EHD, FDB FD, HFD, FDC 35A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature. Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series. Tested in open air.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EHD, FDB FD, HFD, FDC 40A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature. Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series. Tested in open air.
Series C F-Frame Time Current Curves TC01200002E Effective March 2018 ED, EHD, FDB FD, HFD, FDC 45A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature. Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series. Tested in open air.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EHD, FDB FD, HFD, FDC 50A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers 1000.00 Maximum Single Pole Trip Times at 25°C For application and coordination purposes only. Based on cold start at rated ambient temperature.
Series C F-Frame Time Current Curves TC01200002E Effective March 2018 ED, EHD, FDB FD, HFD, FDC 60A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers 1000.00 Maximum Single Pole Trip Times at 25°C For application and coordination purposes only. Based on cold start at rated ambient temperature.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EHD, FDB FD, HFD, FDC 70A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers 1000.00 Maximum Single Pole Trip Times at 25°C For application and coordination purposes only. Based on cold start at rated ambient temperature.
Series C F-Frame Time Current Curves TC01200002E Effective March 2018 ED, EHD, FDB FD, HFD, FDC 80A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature. Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series. Tested in open air.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EHD, FDB FD, HFD, FDC 90A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature. Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series. Tested in open air.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EDB, EDS, EDH, EDC, EHD, FDB FD, HFD, FDC 100A 2, 3 & 4 pole 10000.00 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Catalog Types: ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers 1000.00 For application and coordination purposes only. Based on cold start at rated ambient temperature.
Time Current Curves TC01200002E Effective March 2018 Figure 41. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 110A 2, 3, & 4 pole—Curve Number TC012030EN 44 EATON www.eaton.
Series C F-Frame Time Current Curves TC01200002E Effective March 2018 Figure 42. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC 125A 2, 3, & 4 pole—Curve Number TC012031EN EATON www.eaton.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD FDC 150A 2, 3 & 4 pole 10000.000 Circuit Breaker time/current curves Series C F-Frame Circuit Breakers Maximum Single Pole Trip Times at 25°C 1000.000 Catalog Types: ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EDB, EDS, EDH, EDC, EHD, FDB FD, HFD, FDC 175A 2, 3 & 4 pole 10000.000 Circuit Breaker time/current curves Maximum Single Pole Trip Times at 25°C Series C F-Frame Circuit Breakers Catalog Types: ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD,FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EDB, EDS, EDH, EDC, EHD, FDB FD, HFD, FDC 200A 2, 3 & 4 pole 10000.000 Circuit Breaker time/current curves Maximum Single Pole Trip Times at 25°C Series C F-Frame Circuit Breakers Catalog Types: ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD,FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 ED, EDB, EDS, EDH, EDC, EHD, FDB FD, HFD, FDC 225A 2, 3 & 4 pole 10000.000 Circuit Breaker time/current curves Maximum Single Pole Trip Times at 25°C Series C F-Frame Circuit Breakers Catalog Types: ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, HFD, FDC for two, three and four pole breakers For application and coordination purposes only. Based on cold start at rated ambient temperature.
Time Current Curves TC01200002E Series C F-Frame Effective May 2017 100 kA 100 kA 50 kA 50 kA 10 kA 10 kA 10,000 10,000 100,000 100,000 1 kA 1 kA 500,000 500,000 1,000,000 1,000,000 5,000,000 5,000,000 10,000,000 10,000,000 5 kA 5 kA Available Short Circuit Current, kA kA rmsrms Available Short Circuit Current, 500 kA 500 kA FDC3225 FDC3225 JDC3250 JDC3250 LDC3600 LDC3600 KDC3400 KDC3400 1000 kA 1000 kA Peak Let-Through I2t, A2 sec Peak Let-Through I2t, A2 sec Figure 47.
Time Current Curves TC01200002E Series C F-Frame Effective March 2018 1000 kA 1000 kA Available Short Circuit Current, kA rms Available Short Circuit Current, kA rms FDC3225 FDC3225 JDC3250 JDC3250 KDC3400 KDC3400 LDC3600 LDC3600 500 kA 500 kA 100 kA 100 kA 50 kA 50 kA 10 kA 10 kA 5 kA 5 kA 100,000 100,000 500,000 500,000 1,000,000 1,000,000 5,000,000 5,000,000 10,000,000 10,000,000 1 kA 1 kA Peak Let-Through I2t, 2A2 sec Peak Let-Through I t, A2 sec Figure49.
50 kA 50 kA 100 kA 100 kA EATON www.eaton.com Peak Let-Through Current, kA Peak Let-Through Current, kA Figure 52 Series C Types FDC, JDC, KDC and LDC —600 V (Curve No. AD-29-166C) 1 kA 1 kA 5 kA 5 kA 10 kA 10 kA avail. Ip for 1st avail. Ip for symm. 1/21st cycle symm.
Series C F-Frame Time Current Curves TC01200002E Effective May 2017 Notes: EATON www.eaton.
Time Current Curves TC01200002E Effective March 2018 Series C F-frame circuit breaker time current curves Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com © 2018 Eaton All Rights Reserved Printed in USA Publication No. TC01200002E / TBG001366 March 2018 Eaton is a registered trademark. All other trademarks are property of their respective owners.