Time Current Curves TC01200002E
Effective March 2018
Series C
F-Frame
EATON www.eaton.com
0.01
0.1
1
10
100
1000
10000
1 10 100
Time in Seconds
Current in Multiples of I
r
300 ms
150 ms
Minimum
Commit Time
Maximum total
clearing time
2x
10x
Long Delay Pickup
@ 115% I
r
± 5%
Long Delay
@ 6 × I
r
+0%/-30%
0.001
0.01
0.1
1
1000 10000 100000
Current in Amps
Interrupting
Rating
Determines
End of Curve
Fixed Instantaneous
Override
600V
480V
240V
Figure 6. Digitrip 210+ Trip Units (100 & 225A), Long Delay and Short Delay with Flat Response and Override (LSI, Proles K, J, S, R)
Curve Number TD012001EN, June 2015
Digitrip 210+ Circuit Breaker Time/Current Curves (Phase Current)
Series C F-frame circuit breakers (100A and 225A)
Catalog Types: FDE, HFDE Proles: J, K, R, S
Trip Unit Types: 22 (LSI)
UL/CSA rms Sym. kA, 50/60 Hz
FDE
HFDE
240Vac 480Vac 600Vac 250Vdc
Breaker Type
Interrupting Rating
65 35 18 —
100 65 25 —
A 40A 100A
B 50A 110A
C 60A 125A
D 70A 150A
E 80A 175A
F 90A 200A
G 100A 225A
Rated Amperes
I
r
100A 225A
J 2 150
K 2 300
L 2 I
2
t
M 4 Inst
N 4 150
O 4 I
2
t
P 6 Inst
Q 6 300
R 10 150
S 10 300
SD Prole I
sd
(X l
r
) t
sd
(ms)
Notes:
1 Curve accuracy applies from -20C to +55C. Temperatures above +105C cause an
overtemperature protection trip.
2 There is a memory effect that can act to shorten the long delay. Approximately ve
minutes is required between overloads to completely reset this thermal memory.
3 Total clearing times shown include the response times of the trip unit, the breaker
opening, and the interruption of the current.
4 Short delay pickups settings in multiples of I
r
± 10%. Short delay time accuracy
+0ms/-30ms
5 For high fault current levels an additional xed instantaneous hardware override is