Eaton Advanced ePDU User’s Guide P-164000042—Rev 2 www.eaton.com/ePDU 107
16. Type Y and press [Enter]. The Network Management Card restarts.
Figure 67. SSL Control
SNMP Control
1. Access the Serial interface and log in.
2. Type 1 (Network Management Card Settings) and press [Enter].
3. Type 2 (Network Settings) and press [Enter].
4. Type 3 (Communication Control) and press [Enter].
5. Type 7 (SNMP Control) and press [Enter].
6. Type 1 (SNMP Version) and press [Enter].
7. Choose an SNMP version:
l
Disabled: Type 0 and press [Enter]. The agent is disabled. The MIB cannot be read and no traps are
sent (see Figure 68).
l
SNMPv1: Only SNMPv1 users and SNMPv1 traps are supported. Type 1 and press [Enter].
l
SNMPv3: Only SNMPv3 users and SNMPv3 traps are supported. Type 2 and press [Enter].
l
SNMPv1 & v3: Both SNMPv1 and SNMPv3 users and traps are supported. Type 3 and press [Enter].
Figure 68. SNMP Version Status
Hostname
1. Access the Serial interface and log in.
2. Type 1 (Network Management Card Settings) and press [Enter].
3. Type 2 (Network Settings) and press [Enter].
4. Type 4 (Hostname) and press [Enter].