Notes Minimum length 10 mm.
Climatic environmental conditions
Operating ambient temperature °C -25 - +60, in accordance with IEC 60068-2-1
Condensation Take appropriate measures to prevent condensation
Storage ϑ °C -40 - +80
Main conducting paths
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/2
Rated operational voltage U
e
V 42 - 550
Rated operational current
AC-51 I
e
A 0.15 - 2.40
AC-53a I
e
A 0.15 - 2.4
Heat dissipation P
V
W 1.1 - 3.3
Static heat dissipation, non-current-dependent P
vs
W 1
Basic insulation to IEC/EN60947-1
Between supply, control, and switching voltages V AC 500
between feedback signal output and switch voltage V AC 500
Safe isolation to IEC/EN60947-1
Between supply, control, and switching voltages V AC ≦ 300
between feedback signal output and switch voltage V AC ≦ 300
Safe isolation to EN 50178
Between supply, control, and switching voltages V AC 500
between feedback signal output and switch voltage V AC 500
Current measurement
Setting range of overload releases I
r
A_x 0,18 - 2,4
Release class CLASS 10
Recovery time t
W
min. 2 (manual startup)
20 (automatic restart)
Balance monitoring
Magnitude I
max
> I
rated
((I
max
- I
min
)/I
max
) % If ≧ 33, pick-up time of 120 s
If ≧ 67, pick-up time of 1.8 s
Magnitude I
max
< I
rated
((I
max
- I
min
)/I
rated
) % If ≧ 33, pick-up time of 120 s
If ≧ 67, pick-up time of 1.8 s
Short-circuit rating
Type “1” coordination
Short-circuit protective device 50 kA, 500 V AC: Fuse 16 A gG/gL
50 kA, 415 V AC: PKM0-4
15 kA, 415 V AC: PKM0-6,3
Control section
Input data
Supply voltage U
AUX
V DC A1 - A2: 24 (-20 - +25 %)
Residual ripple on the input voltage % ≦ 5
Supply voltage "confirm Off" U
AUX
V DC < 5
Input current mA 40
Note on input current without feedback signal
Actuating circuit (ON, L, R)
Switching level "Low" V -3 - +9.6 V DC
Switching level "confirm Off" V < 5 V DC
Switching level "High" V 19.2 - 30 V DC
Input current mA 5
Feedback outputs
Notes Contacts 95, 96 or 98
Contacts
CO = changeover 1 CO
Rated operational voltage U
e
V AC/DC 250
Rated operational current
AC-15