Data Sheet

Tools
Pozidriv screwdriver Size 2
Standard screwdriver mm 1 x 6
Auxiliary power circuit
Rated insulation voltage U
i
V 300
Rated insulation voltage U
i
V 400
Value applies starting with release 001.
Rated operational current I
e
A
AC--14
Make contact
300 V I
e
A 3
380 V 400 V 415 V I
e
A 3
Value applies starting with release 001.
Break contact
300 V I
e
A 3
380 V 400 V 415 V I
e
A 3
Value applies starting with release 001.
AC-15
Make contact
220 V 230 V 240 V I
e
A 3
300 V I
e
A 1
380 V 400 V 415 V I
e
A 1
Value applies starting with release 001.
Break contact
220 V 230 V 240 V I
e
A 3
300 V I
e
A 1
380 V 400 V 415 V I
e
A 1
Value applies starting with release 001.
Max. short-circuit protective device
Fuse gG/gL A 6
Control circuit
Rated insulation voltage U
i
V 240
Rated operational voltage U
e
V 230
Pick-up and drop-out values x U
e
0.85 - 1.1
Power consumption
AC VA 3.5
DC W 2
Trip at approx. 3600
Recovery at approx. 1600
Sensor circuit Sensor circuit parameters at U
S
and +20 °C:
max. Cable length to sensor 250m (not insulated)
Total cold resistance ∑ R
K
≦ 1500 Ω
- R
T1-T2
(T1, T2 shorted): I
T1-T2
= 1.9 mA
- R
T1-T2
(4 kΩ): U
T1-T2
= max. 3 V DC, I
T1-T2
= max. 0.8 mA
- R
T1-T2
(T1, T2 open): U
T1-T2
= 5.1 V DC typ. (5.5 V DC max.)
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD)
applied standard IEC/EN 61000-4-2
Air discharge kV 8
Contact discharge kV 6
Electromagnetic fields (RFI)
applied standard IEC/EN 61000-4-3
V/m 80 - 1000 MHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1
Radio interference suppression EN 55011
Class B
Burst kV Supply cables: 2
06/16/2021 Eaton 066400 ED2021 V80.0 EN 2 / 5