Datasheet

04/16/2013 HPL-ED2013 V1.0 EN 2 / 4
Terminals IP20
Weight kg 0.1
Terminal capacities
mm
2
Solid
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
Flexible with ferrule
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
Solid or stranded AWG 1 x (20 - 14)
Contacts
Rated impulse withstand voltage U
imp
V
AC
6000
Overvoltage category/pollution degree III/2
Rated insulation voltage U
i
V
AC
600
Rated operational voltage U
e
V
AC
440
Safe isolation to EN 61140
between coil and auxiliary contacts V
AC
250
between the auxiliary contacts V
AC
250
Making capacity
AC-14 cosϕ = 0.3 400 V A 48
AC-15 cosϕ = 0.3 220 V A 50
DC-11 L/R - 40 ms x I
e
1.1
Breaking capacity
AC-14 cosϕ = 0.3 440 V A 3
AC-15 cosϕ = 0.3 220 V A 3
DC-11 L/R - 40 ms x I
e
1.1
Rated operational current I
e
A
AC--14
440 V I
e
A 3
AC-15
220 V (230 V) I
e
A 3
DC-11
Note Making and breaking conditions to DC13, time constant as stated
L/R max. 15 ms A
24 V I
e
A 1.5
L/R max. 50 ms A 1.2
Conv. thermal current I
th
A 6
Short-circuit rating without welding
Note When supplied directly from mains or transformer > 1000 VA
Max. fuse, make contacts A
gG/
gL
6
Max. fuse, break contacts A
gG/
gL
6
Max. overcurrent protective device, 220/230 V Type FAZ-B4/1-HI
Magnet�systems
Voltage tolerance x U
c
Pick-up voltage x U
s
Min. pick-up voltage, AC operated x U
c
0.85
Pick-up voltage AC operated, max. x U
c
1.1
Pick-up voltage DC operated, min. x U
c
0.7
Max. pick-up voltage, DC operated x U
c
1.1
Power consumption
Pick-up AC VA 2