Datasheet

05/22/2017 278672 - HPL-ED2017 V32.0 EN 1 / 8
Over�current�switch,�13A,�1Np,�C-Char,�AC
Part�no. FAZ-C13/1N
Article�no. 278672
Catalog�No. FAZ-C13/1N
Similar to illustration
Delivery�program
Basic function Miniature circuit-breakers
Number of poles 1 pole+N
Tripping characteristic C
Application Switchgear for industrial and advanced commercial applications
Rated current I
n
A 13
Rated switching capacity acc. to IEC/EN 60947-2 kA 15
Product range FAZ
Technical�data
Electrical
Standards IEC/EN 60947-2
IEC/EN 60898
Rated operational voltage U
e
V
U
e
V AC 240/415
V DC 60 (per pole)
Rated switching capacity acc. to IEC/EN 60947-2 kA 15
Operational switching capacity kA 7.5
Characteristic B, C, D
Max. back-up fuse A gL/gG 125
Selectivity Class 3
Lifespan Operations > 10000
Direction of incoming supply as required
Mechanical
Standard front dimension mm 45
Enclosure height mm 80
Terminal protection Finger and back-of-hand proof to BGV A2
Mounting width per pole mm 17.5
Mounting IEC/EN 60715 top-hat rail
Degree of Protection IP20, IP40 (when fitted)
Terminals top and bottom Twin-purpose terminals
Terminal capacities
mm
2
mm
2
1 x 25
mm
2
2 x 10
Thickness of busbar material mm 0.8 … 2
Mounting position As required
Design�verification�as�per�IEC/EN�61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 13
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 2.9
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -40
Operating ambient temperature max. °C 75