Datasheet
05/23/2017 240772 - HPL-ED2017 V32.0 EN 1 / 4
Over�current�switch,�3A,�1p,�B-Char,�AC
Part�no. FAZT-B3/1
Article�no. 240772
Catalog�No. FAZT-B3/1
Similar to illustration
Delivery�program
Basic function Miniature circuit-breakers
Number of poles 1 pole
Tripping characteristic B
Application Switchgear for industrial and advanced commercial applications
Rated current I
n
A 3
Rated switching capacity acc. to IEC/EN 60947-2 kA 25
Product range FAZ-T
Technical�data
Electrical
Standards IEC/EN 60947-2
Rated voltage V 240/415
Rated frequency f Hz 50/60
Rated switching capacity kA 25
Characteristic B, C, D
Lifespan Operations 20000
Direction of incoming supply as required
Mechanical
Standard front dimension mm 45
Enclosure height mm 80
Mounting width per pole mm 17.5
Mounting Quick attachment with 3 latch positions for top-hat rail IEC/EN 60715
Degree of Protection IP20
Terminals top and bottom Twin-purpose terminals
Terminal protection Finger- and back-of-hand proof according to BGV A3 and ÖVE-EN 6
Terminal capacities
mm
2
1 - 25
Tightening torque Nm 2 - 2.4
Thickness of busbar material mm 0.8 (exept N 0.5 SU)
Mounting position As required
Design�verification�as�per�IEC/EN�61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 3
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 2.5
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -40
Operating ambient temperature max. °C 75
linear, per +1 °C, results in a 0.5% reduction of current carrying capacity
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.