Cut Sheet

Volume 4—Circuit Protection CA08100005E—August 2015 www.eaton.com V4-T2-261
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2.3
Molded Case Circuit Breakers
Series C
MCPs for Application with Motor Starters Equipped with Electronic Overload Relays
600 Vac Maximum, 250 Vdc Maximum 600 Vac Maximum, 250 Vdc Maximum, continued
Notes
1
Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA
value shown. Where a 13 x setting is required for an intermediate FLA value, alternate cam
settings and/or MCP ratings should be used.
2
For DC applications, actual trip levels are approximately 40% higher than values shown.
3
Settings above 130A are for special applications. NEC Article 430.110(a) requires the
ampere rating of the disconnecting means to be not less than 115% of the motor full load
ampere rating.
HMCP 25–100 A come with line and load steel body terminals, 3T100FB.
HMCPS 3–100 A come with line and load steel body terminals, 3T100FB. HMCPS 150A come
with line and load steel body terminals, 3T150FB.
NEMA
Starter
Size
Cont.
Amps
Cam
Setting
Motor Full
Load Current
Amperes
(FLA)
1
MCP
Trip
Setting
2
MCP
Catalog
Number
0 3 A 0.69–0.91 9 HMCPS003A0C
B 0.92–1.0 12
C 1.1–1.2 15
D 1.3–1.5 18
E 1.6–1.7 21
F 1.8–1.9 24
G 2.0–2.2 27
H 2.3–2.5 30
0 7 A 1.5–2.0 21 HMCPS007C0C
B 2.1–2.5 28
C 2.6–3.1 35
D 3.2–3.6 42
E 3.7–3.9 49
F 4.3–4.7 56
G 4.8–5.2 63
H 5.3–5.7 70
0 15 A 3.4–4.5 45 HMCPS015E0C
B 4.6–5.6 60
C 5.7–6.8 75
D 6.9–7.9 90
E 8.0–9.1 105
F 9.2–10.3 120
G 10.4–11.4 135
H 11.5–12.6 150
1 30 A 6.9–9.1 90 HMCPS030H1C
B 9.2–11.4 120
C 11.5–13.7 150
D 13.8–16.0 180
E 16.1–18.3 210
F 18.4–20.6 240
G 20.7–22.9 270
H 23.0–25.2 300
2 50 A 11.5–15.2 150 HMCPS050K2C
B 15.3–19.1 200
C 19.2–22.9 250
D 23.0–26.8 300
E 26.9–30.6 350
F 30.7–34.5 400
G 34.6–38.3 450
H 38.4–42.1 500
NEMA
Starter
Size
Cont.
Amps
Cam
Setting
Motor Full
Load Current
Amperes
(FLA)
1
MCP
Trip
Setting
2
MCP
Catalog
Number
3 100 A 23.0–30.6 300 HMCPS100R3C
B 30.7–38.3 400
C 38.4–46.0 500
D 46.1–53.7 600
E 53.8–61.4 700
F 61.5–69.1 800
G 69.2–76.8 900
H 76.9–84.5 1000
4 150 A 34.6–46.0 450 HMCPS150T4C
B 46.1–57.5 600
C 57.6–69.1 750
D 69.2–80.6 900
E 80.7–92.2 1050
F 92.3–103.7 1200
G 103.8–115.2 1350
H 115.3–126.7 1500
4 150 A 57.0–75.0 750 HMCPS150U4C
B 76.0–95.0 1000
C 96.0–114.0 1250
D 115.0–130.7 1500
E
3
1750
F
3
2000
G
3
2250
H
3
2500