Power Breakers, Contactors and Fuses
Medium Voltage Power Contactors
SL Series Fuses
Fuse Application Table for SL Contactors—7.2 kV/160A
Fuse Application Table for SL Contactors—7.2 kV/200A
Fuse Application Table for SL Contactors—7.2 kV/360A
Fuse Application Table for SL Contactors—7.2 kV/400A
Notes
1
For FLA >180, maximum acceleration time = 4.5 seconds.
2
For FLA >360, maximum acceleration time = 6 seconds.
Fuse selections based on LRC = FLA x 6 with acceleration time of 10 seconds except where
otherwise noted.
Motor
FLA Voltage
Suggested
Eaton Fuse Rating
Minimum
Opening Time
11–18 2400–4800 5BCLS-30 30–1R 30
18–31 2400–4800 5BCLS-2R 70–2R 30
31–46 2400–4800 5BCLS-3R 100–3R 30
46–62 2400–4800 5BCLS-4R 130–4R 30
62–74 2400–4800 5BCLS-5R 150–5R 30
74–93 2400–4800 5BCLS-6R 170–6R 30
93–137 2400–4800 5BCLS-9R 200–9R 130
137–160 2400–4800 5BCLS-12R 230–12R 130
11–34 5500–6600 7BCLS-2R 70–2R 30
34–46 5500–6600 7BCLS-3R 100–3R 30
46–56 5500–6600 7BCLS-4R 130–4R 30
56–68 5500–6600 7BCLS-5R 150–5R 30
68–85 5500–6600 7BCLS-6R 170–6R 30
85–137 5500–6600 7BCLS-9R 200–9R 50
137–160 5500–6600 7BCLS-12R 230–12R 250
Motor
FLA Voltage
Suggested
Eaton Fuse Rating
Minimum
Opening Time
11–18 2400–4800 5BCLS-30 30–1R 30
18–31 2400–4800 5BCLS-2R 70–2R 30
31–46 2400–4800 5BCLS-3R 100–3R 30
46–62 2400–4800 5BCLS-4R 130–4R 30
62–74 2400–4800 5BCLS-5R 150–5R 30
74–93 2400–4800 5BCLS-6R 170–6R 30
93–137 2400–4800 5BCLS-9R 200–9R 130
137–200
1
2400–4800 5BCLS-12R 230–12R 130
11–34 5500–6600 7BCLS-2R 70–2R 30
34–46 5500–6600 7BCLS-3R 100–3R 30
46–56 5500–6600 7BCLS-4R 130–4R 30
56–68 5500–6600 7BCLS-5R 150–5R 30
68–85 5500–6600 7BCLS-6R 170–6R 30
85–137 5500–6600 7BCLS-9R 200–9R 50
137–200
1
5500–6600 7BCLS-12R 230–12R 250
Motor
FLA Voltage
Suggested
Eaton Fuse Rating
Minimum
Opening Time
11–18 2400–4800 5BCLS-30 30–1R 30
18–31 2400–4800 5BCLS-2R 70–2R 30
31–46 2400–4800 5BCLS-3R 100–3R 30
46–62 2400–4800 5BCLS-4R 130–4R 30
62–74 2400–4800 5BCLS-5R 150–5R 30
74–93 2400–4800 5BCLS-6R 170–6R 30
93–137 2400–4800 5BCLS-9R 200–9R 130
137–187 2400–4800 5BCLS-12R 230–12R 130
187–200 2400–4800 5BCLS-12R 230–12R 130
200–360 2400–4800 N/A
11–34 5500–6600 7BCLS-2R 70–2R 30
34–46 5500–6600 7BCLS-3R 100–3R 30
46–56 5500–6600 7BCLS-4R 130–4R 30
56–68 5500–6600 7BCLS-5R 150–5R 30
68–85 5500–6600 7BCLS-6R 170–6R 30
85–137 5500–6600 7BCLS-9R 200–9R 50
137–200
1
5500–6600 7BCLS-12R 230–12R 250
200–360 5500–6600 N/A
Motor
FLA Voltage
Suggested
Eaton Fuse Rating
Minimum
Opening Time
11–18 2400–4800 5BCLS-30 30–1R 30
18–31 2400–4800 5BCLS-2R 70–2R 30
31–46 2400–4800 5BCLS-3R 100–3R 30
46–62 2400–4800 5BCLS-4R 130–4R 30
62–74 2400–4800 5BCLS-5R 150–5R 30
74–93 2400–4800 5BCLS-6R 170–6R 30
93–137 2400–4800 5BCLS-9R 200–9R 30
137–187 2400–4800 5BCLS-12R 230–12R 30
187–273 2400–4800 5BCLS-18R 390–18R 50
273–400
2
2400–4800 5BCLS-24R 450–24R 130
11–34 5500–6600 7BCLS-2R 70–2R 30
34–46 5500–6600 7BCLS-3R 100–3R 30
46–56 5500–6600 7BCLS-4R 130–4R 30
56–68 5500–6600 7BCLS-5R 150–5R 30
68–85 5500–6600 7BCLS-6R 170–6R 30
85–137 5500–6600 7BCLS-9R 200–9R 30
137–187
1
5500–6600 7BCLS-12R 230–12R 30
273–400
2
5500–6600 7BCLS-24R 450–24R 250