Cut Sheet

V4-T1-84 Volume 4—Circuit Protection CA08100005E—August 2015 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Accessories Technical Data
Description
FAZ-XHIN
FAZ-XAM002 FAZ-XAA-C FAZ-XUA
Electrical
Contact function 1A + 1B
2 C/O
Rated operational voltage U
n
250 Vac 115 Vac
230 Vac
400 Vac
Voltage range 12–110 Vac
12–60 Vdc
Voltage range 110–415 Vac
110–230 Vdc
Closing threshold [x U
n
]—0.8
Tripping threshold [x U
n
]—0.5
Rated frequency ƒ 50/60 Hz 50/60 Hz 50/60 Hz
General use (UL/CSA)
AC—230/240 Vac
DC—110/120 Vdc
2/2A
0.5/0.5A
Pilot duty A600/Q600
Conventional free air thermal current I
th
4A
Rated operational current
AC-13 I
e
AC-15 I
e
DC-13 I
e
3A (250 Vac)
2A (250 Vac)
0.5A (110 Vdc)
Rated insulation voltage U
i
250 Vac
Minimum operating voltage per contract U
min
5 Vdc
Rated impulse withstand voltage (1.2/50) U
imp
2.5 kV
Rated conditional short-circuit current with 6A backup fuse I
SC
1 kA
Max. admissible backup fuse 4A gL
Mechanical
Standard front dimension 45 mm 45 mm 45 mm
Device height 80 mm 80 mm 80 mm
Mounting width 8.8 mm 17.6 mm 17.8 mm
Mounting On MCB IEC/EN 60715 top-hat rail IEC/EN 60715 top-hat rail
Degree of protection enclosed
IP40 IP40 IP40
Terminal protection Protection against
electric shock to IEC 536
Protection against
electric shock to IEC 536
Protection against
electric shock to IEC 536
Terminals Lift terminals Twin-purpose terminals Twin-purpose terminals
Terminal capacity
Solid
Flexible
0.5–2.5 mm
2
0.5–2.5 mm
2
1–2.5 mm
2
1–2.5 mm
2
2 x (1–2.5) mm
2
2 x (1–2.5) mm
2
Tightening torque of terminal screws 0.8–1.0 Nm (7–9 lb-in) 2.4 Nm (21 lb-in) 0.8 Nm (7 lb-in)