Datasheet

11/30/2015 167902 - HPL-ED2015 V17.0 EN 1 / 4
Digital�residual�current�circuit-breaker,�63A,�4p,�300mA,�type�S/B
Part�no. FRCDM-63/4/03-S/B
Article�no. 167902
Catalog�No. FRCDM-63/4/03-S/B
Similar to illustration
Delivery�programme
Basic function Residual current circuit breakers , digital
Pole 4 pole
Application Switchgear for industrial and commercial applications
Rated current I
n
A 63
Rated short-circuit strength I
cn
kA 10 with back-up fuse
Rated fault current I
ΔN
A 0.3
Type Type S/B
Tripping A selective switch off
Product range FRCdM
Sensitivity All current sensitive
Impulse withstand current surge-proof 5 kA
Contact sequence
Technical�data
Electrical
Types conform to IEC/EN 61008
IEC/EN 62423
Current test marks As per inscription
Tripping A 40 ms delay - selective switch off
Rated operating voltage U
n
V AC 240/415
Rated frequency f Hz 50
Limit values of the operating voltage
electronic V AC 50 - 456
Test circuit V AC 196 - 456
Rated fault current I
Δn
mA 300
Sensitivity All current sensitive
Rated insulation voltage U
i
V 440
Rated impulse withstand voltage U
imp
kV 4 (1.2/50μs)
Rated short-circuit strength I
cn
kA 10 with back-up fuse
Impulse withstand current 5 kA (8/20 μs) surge-proof
Max. admissible back-up fuse
Short-circuit gG/gL A 63
Overload gG/gL A 63
Rated making and breaking capacity / Rated residual making and breaking
capacity
I
m
/ I
Δm
A 630
lifespan
Electrical Operations
2000
Mechanical Operations
10000
Dry�auxiliary�contact
Rated switching capacity
30 VDC (resistive load) A 2
240 VAC (resistive load) A 0.25

Summary of content (4 pages)