Cut Sheet

Input Ratings
Input voltage (
V
in
) 200–240 Vac, 380–480 Vac, –10%/+10%
Input frequency (
f
in
) 50/60 Hz (variation up to 47–66 Hz)
Connection to power Once per minute or less
(typical operation)
Short circuit withstand rating 100 kAIC
Output Ratings
Output voltage 0 to Vin/Uin line voltage in
Continuous output current Ambient temperature max. 104°F (40°C)
IL overload 1.1 x IL (1 min./10 min.)
Overload current 110% (1 min./10 min.)
Initial output current 150% for two seconds
Output frequency 0 to 320 Hz
Frequency resolution 0.01 Hz
Ambient Conditions
Operating Temperature 14 degree’s F (-10° C), no frost to 104
degree’s F (40° C). (Drive can operate at
122° F (50° C), See Catalog for derating)
Storage Temperature -40 degree’s F (-40° C) to 158° F (70° C)
Relative Humidity 0 to 95%, noncondensing, non-corrosive,
no dripping water
Altitude 100% load capacity up to 3280ft (1000m)
1% derating for each 328ft (100m) above
3280ft (1000m); max. 9842ft (3000m);
380 - 480V
Protections
Overcurrent protection Yes
Overvoltage protection Yes
DC bus regulation anti-trip Yes (accelerates or decelerates the load)
Undervoltage protection Yes
Earth fault protection Yes (in case of earth fault in motor or
motor cable, only the frequency converter
is protected)
Input phase supervision Yes (trips if any of the input phases are
missing)
Motor phase supervision Yes (trips if any of the output phases are
missing)
Overtemperature protection Yes
Motor overload protection Yes
Motor stall protection Yes
Motor underload protection Yes
Short circuit protection Yes
Surge protection Yes (varistor input)
Conformed coated(varnished) boards Yes (prevents corrosion)