18 H-Max Series Adjustable Frequency Drive MN04008005E—September 2011 www.eaton.com
H-Max Series Drives—380–480 Volt
NEMA Type 1/IP21 or NEMA Type 12/IP54
H-Max Series Adjustable Frequency Drive Option Boards
Note
For sizing reference, full-load motor running currents—UL508C.
FS
Frame
Size
Drive Input Rated Current and hp
Drive
Input
Amps
NEC Motor
60 Hz
460V Amps
De-Rated
Assigned
Motor Ratings _ Can Be:
Low Overload
Full Load
Amps at 40°C
460V
60 Hz
Horsepower
Low Overload
Full Load
Amps at 50°C
Open Drive
kW
400V
50 Hz
1 = N1 = IP21
2 = N12 = IP54
Catalog Number
FS4 3.4 1.5 3.4 3 2.6 1.1 HMX34AG3D42_-N
4.8 2 4.6 3.4 3.4 1.5 HMX34AG4D82_-N
5.6 3 5.4 4.8 4.3 2.2 HMX34AG5D62_-N
8.0 5 8.1 7.6 5.6 3.0 HMX34AG8D02_-N
9.6 5 9.3 N/A 8 4 HMX34AG9D62_-N
12 7.5 11.3 11 9.6 5.5 HMX34AG0122_-N
FS5 16 10 15.4 14 12 7.5 HMX34AG0162_-N
23 15 21.3 21 16 11 HMX34AG0232_-N
31 20 28.4 27 23 15 HMX34AG0312_-N
FS6 38 25 36.7 34 31 18.5 HMX34AG0382_-N
46 30 43.6 40 38 22 HMX34AG0462_-N
61 40 58.2 52 46 30 HMX34AG0612_-N
FS7 72 50 67.5 65 61 37 HMX34AG0722_-N
87 60 85.3 77 72 45 HMX34AG0872_-N
105 75 100.6 96 87 55 HMX34AG1052_-N
FS8 140 100 139.4 124 105 75 HMX34AG1402_-N
170 125 166.5 156 140 90 HMX34AG1702_-N
205 150 200 180 170 110 HMX34AG2052_-N
FS9 261 200 258 240 205 132 HMX34AG2612_-N
310 250 303 302 251 160 HMX34AG3102_-N
Option Board
Part Number
Assigned to
Control
Module Slot: Description
XMX-IO-B1-A D or E Expanded 6 digital output—two outputs are programmable as digital inputs or outputs
XMX-IO-B2-A D or E Expanded relay outputs—two programmable relays (each with a NO and NC contact) and thermistor input
XMX-IO-B4-A D or E Expanded analog inputs and outputs—one analog input and two analog outputs (isolated)
XMX-IO-B5-A D or E Expanded relay outputs—contains three programmable relays (one NO contact each)
XMX-IO-B9-A D or E Accepts up to five AC inputs (42–240 Vac) and one relay output (NO)
XMX-IO-BF-A D or E Expanded analog and digital output—one analog, one digital, and one relay output (NO)
XMX-COM-C4-A D or E LonWorks
®
communication