Installation Manual

Installation Requirements
22 H-Max Series Adjustable Frequency Drive MN04008005E—September 2011 www.eaton.com
Power Wiring Selection
Line (Mains) and Motor Cable Installation
Motor cable connections are made to terminals U/T
1
, V/T
2
,
and W/T
3
.
Cable Selection: Power and Motor Leads
Use UL approved heat-resistant copper cables only
75°C or higher for all units rated <480V
90°C or higher for all 480V units
Line voltage/mains should be Class 1 wire only outside
North America
Refer to the following tables for cable sizing guidelines
The input line and motor cables must be sized in accordance
with the rated H-Max AFD input current.
If motor temperature sensing is used for overload protection,
the output cable size may be selected based on the motor
specifications.
Maximum symmetrical supply current is 100,000A RMS for
all size H-Max AFDs.
Input Fusing
Fuses are rated based on H-Max rated output current.
Use Class T (UL or CSA) or type gG/gL (IEC 60269-1).
Refer to Pages 43, 44, and 45 for proper fuse size selection.
Fuses with an operating speed of less than 0.4 seconds may
be used including the following types:
High Speed J (UL and CSA)
aR (UL recognized, IEC 60269-4)
gS (IEC 60269-4)
Consult with Eaton Electrical for further information on fusing
requirements.
North America 208–240V Page 43
North America 380–480V Page 44
All other International 380–600V Page 45