Power Connection Tightening Torque
Note: Strip the motor and power cables as shown in figure on next page.
Spacing Between Parallel Motor Cables Maximum Cable Length by Frame Size without DV/DT
Protected C2 Ratings
Fame Size Voltage hp (VT) kW Amperes
Tightening
Torque
(in-lbs)
Tightening
Torque
(Nm)
FS4 230 Vac 0.75-4 0.75–3.0 3.7–12.5 5 0.6
400 Vac 1.1–5.5 3.4–12
460 Vac 1.5–7.5 3.4–12
FS5 230 Vac 5–10 4–7.5 18–31 13 1.5
400 Vac 7.5–15 16–31
460 Vac 10–20 16–31
FS6 230 Vac 15–20 11–15 48–62 35 4
400 Vac 18.5–30 38–61
460 Vac 25–40 38–61
FS7 230 Vac 25–40 18.5–30 75–105 88 10
400 Vac 37–55 72–105
460 Vac 50–75 72–105
FS8 230 vac 50–75 37–55 140–205 170/8 20/9
400 Vac 75–110 140–205
460 Vac 100–150 140–205
FS9 230 Vac 100–125 75–90 261–310 354/195 40/22
400 Vac 132–160 261–310
460 Vac 200–250 261–310
Cable Length Distance Between Cables
Less than 164 ft (50 m) 1 ft (0.3m)
Less than 657 ft (200 m) 3 ft (3.3m)
Frame Size Maximum Cable Length
FS4 328 ft (100m)
FS5 493 ft (150m)
FS6
FS7 657 ft (200m)
FS8 657 ft (200m)