Checking the Cable and Motor Insulation
1. Check the motor cable insulation as follows:
Disconnect the motor cable from terminals U, V and W
of the H-Max Series drive and from the motor
Measure the insulation resistance of the motor cable
between each phase conductor as well as between
each phase conductor and the protective ground
conductor
The insulation resistance must be >1 mohm
2. Check the input power cable insulation as follows:
Disconnect the input power cable from terminals L1, L2
and L3 of the H-Max Series drive and from the utility line
feeder
Measure the insulation resistance of the input power
cable between each phase conductor as well as
between each phase conductor and the protective
ground conductor
The insulation resistance must be >1 mohm
3. Check the motor insulation as follows:
Disconnect the motor cable from the motor and open
any bridging connections in the motor connection box
Measure the insulation resistance of each motor
winding. The measurement voltage must equal at least
the motor nominal voltage but not exceed 1000V
The insulation resistance must be >1 mohm