Installation Manual

Appendix A
40 H-Max Series Adjustable Frequency Drive MN04008005E—September 2011 www.eaton.com
H-Max Technical Data, continued
Attribute Description Specification
Ambient conditions,
continued
Vibration:
EN61800-5-1
EN60668-2-6
5–150 Hz
Displacement amplitude:
1 mm (peak) at 5–15.8 Hz (FS4–FS9)
Maximum acceleration amplitude:
1g at 15.8–150 Hz (FS4–FS9)
Shock:
EN61800-5-1
EN60068-2-27
UPS drop test (for applicable UPS weights)
Storage and shipping: Maximum 15g, 11 ms (in
package)
Enclosure class IP21/Type 1 standard in entire kW/hp range
IP54/Type 12 option
Note: Keypad required for IP54/Type12
EMC (at default settings) Immunity Fulfils EN61800-3 (2004), first and second
environment
Emissions +EMC2: EN61800-3 (2004), Category C2
The drive can be modified for IT-networks
Noise level Average noise level (cooling fan)
sound power level in dB(A)
FS4: 65 FS7: 77
FS5: 70 FS8: 86
FS5: 77 FS9: 87
Safety EN61800-5-1 (2007), CE, cUL (see nameplate for more
detailed approvals)
Protections Overvoltage trip limit 240V drives: 456V
480V drives: 911V
Undervoltage trip limit Depends on supply voltage (0,8775*supply voltage):
Supply voltage 240V: Trip limit 211V
Supply voltage 400V: Trip limit 351V
Supply voltage 480V: Trip limit 421V
Earth fault protection Yes
Mains supervision Yes
Motor phase supervision Yes
Overcurrent protection Yes
Unit overtemperature protection Yes
Motor overload protection Yes
Motor stall protection Yes
Motor underload protection Yes
Short-circuit protection of 24V
and 10V reference voltages
Yes