Installation Manual

Appendix A
H-Max Series Adjustable Frequency Drive MN04008005E—September 2011 www.eaton.com 41
Technical Information on Control Connections
Standard I/O Board
Terminal Signal Description
1 Reference output 10V, 3%: Maximum current 10 mA
2 Analog input, voltage or current Analog input channel 1
0–10V (Ri = 200 kohms)
4–20 mA (Ri = 250 ohms)
Resolution 0.1%, accuracy ±1%
Selection V/mA with DIP switches
Short-circuit protected
3 Analog input common (current) Differential input if not connected to ground:
Allows ±20V differential mode voltage to GND
4 Analog input, voltage or current Analog input channel 2
Default:
4–20 mA (Ri = 250 ohms)
0–10V (Ri = 200 kohms)
Resolution 0.1%, accuracy ±1%
Selection V/mA with DIP switches
Short-circuit protected
5 Analog input common (current) Differential input if not connected to ground:
Allows 20 differential mode voltage to GND
6 24V auxiliary voltage 24V, ±10%, maximum voltage ripple <100m Vrms,
maximum 250 mA
Dimensioning: Maximum 1000 mA/control unit
Short-circuit protected
7 I/O ground Ground for reference and controls (connected
internally to frame earth through 1 mohms)
8 Digital input 1 Positive or negative logic
Ri = minimum 5 kohms
0–5V = “0”
15–30V = “1”
9 Digital input 2
10 Digital input 3
11 Common A for DIN1–DIN6 Digital inputs can be disconnected from ground
12 24V auxiliary voltage 24V, ±10% maximum voltage ripple <100m Vrms,
maximum 250 mA
Dimensioning: Maximum 1000 mA/control unit
Short-circuit protected
13 I/O ground Ground for reference and controls (connected
internally to frame earth through 1 mohms)
14 Digital input 4 Positive or negative logic
Ri = minimum 5 kohms
0–5V = “0”
15–30V = “1”
15 Digital input 5
16 Digital input 6
17 Common A for DIN1–DIN6 Digital inputs can be isolated from ground
18 Analog signal (+output) Analog output channel 1, selection 0–20 mA,
load <500 ohms
Default:
0–20 mA
0–10V
Resolution 0.1%, accuracy ±2%
Selection V/mA with DIP switches
Short-circuit protected
19 Analog output common
30 24V auxiliary input voltage Can be used as external power backup for the
control unit
A RS485 Differential receiver/transmitter
Set bus terminal with DIP switches
B RS485