H-Max Series Adjustable Frequency Drive MN04008005E—September 2011 www.eaton.com 43
Appendix B
Cable Power and Motor Wiring Guidelines
See Page 24 for cable stripping guidelines.
North America Cable and Fuse Sizes—208–240 Vac Ratings
Note:
1. If power cubes are used, a UL recognized Type T fuse is recommended.
2. Based on maximum environment of 104°F (40°C).
3. If bypass is used, a UL recognized Type T fuse is recommended.
Frame
Amp
Suffix hp
NEC
Motor
Amp
Rating
at
208 Vac
NEC
Motor
Amp
Rating
at
230 Vac
AFD
I(L)
Amps
at
40°C
AFD
I(L)
Amps
at
50°C
[kW]
230V
at
50 Hz
Fuse
Rating
(Class T)
NEC Wire Size
(AWG)
Terminal
Connection Size
(AWG)
Line
and
Motor Ground
Line
and
Motor Ground
FS4 3D7 0.75 3.5 2.2 3.7 2.6 0.55 10 14 14 24–10 18–10
4D8 1.0 4.6 4.2 4.8 3.7 0.75 10 14 14 24–10 18–10
6D6 1.5 6.6 6.0 6.6 4.6 1.1 10 14 14 24–10 18–10
8D0 2 7.5 6.8 8.0 6.6 1.5 10 14 14 24–10 18–10
011 3 10.6 9.6 11 8.0 2.2 15 14 14 24–10 18–10
012 4 N/A N/A 12 9.0 3 15 14 14 24–10 18–10
FS5 018 5 16.7 15.2 18 12.5 4 20 12 12 20–6 18–8
024 7.5 24.2 22 24 18.0 5.5 30 10 10 20–6 18–8
031 10 30.8 28 31 25.0 7.5 40 8 10 20–6 18–8
FS6 048 15 46.2 42 48 31.0 11 60 4 8 14–0 14–2
062 20 59.4 54 62 48 15 80 3 8 14–0 14–2
FS7 075 25 74.9 68 75 62 18.5 100 2 8 10–2/0 10–2/0
088 30 88 80 88 75 22 110 1 6 10–2/0 10–2/0
105 40 114 104 105 88 30 125 2/0 6 10–2/0 10–2/0
FS8 140 50 143 130 140 114 37 175 2/0 6 1–350
kcmil
1–350
kcmil
170 60 169 154 170 140 45 200 250
kcmil
6 1–350
kcmil
1–350
kcmil
205 75 211 192 205 170 55 250 350
kcmil
4 1–350
kcmil
1–350
kcmil
FS9 261 100 273 248 261 211 75 350 500
kcmil
4 1–350
kcmil
1–350
kcmil
310 125 343 312 310 251 90 400 2X
250
kcmil
3 1–350
kcmil
1–350
kcmil