Installation Manual

Parameters
H-Max HVAC Drives MN04008006Eā€”January 2012 www.eaton.com 31
Basic Settings
Parameter
Number Parameter Name
Change
in Run Min. Max. Default ID Values
P2.3.9.1 Start logic Y 0 3 1 1304 0 = Normal
1 =Intlk start
2 = Intlk Time Start
3 = Delay start
P2.3.9.2 INTLK Timeout N 0,00 s 320,00 s 5,00 s 1305 See Range
P2.3.9.3 Delay Time N 0,00 s 320,00 s 5,00 s 1306 See Range
P2.3.9.4 Intrlk Stop Mode N 0 1 0 1356 0 = Coasting
1 = Ramping
P2.3.9.5 Interlock 1 Text Y 1 16 1 1315 1 = Ext Interlock Missing!
2 = Run enable Missing!
3 = Vibration Cutout
4 = High motor temperature
5 = Freeze Stat Trip
6 = Low Pressure detect
7 = High Pressure detect
8 = Low water detect
9 = Smoke detect
10 =3-wire Off
11 = Damper Interlock
12 = Open Safety
13 = Seal Leakage
14 = Valve sequence
15 = Megger Shutdown
16 = High Pump Temp
P2.3.9.6 Interlock 2 Text Y 1 16 1 1316 1 = Ext Interlock Missing!
2 = Run enable Missing!
3 = Vibration Cutout
4 = High motor temperature
5 = Freeze Stat Trip
6 = Low Pressure detect
7 = High Pressure detect
8 = Low water detect
9 = Smoke detect
10 =3-wire Off
11 = Damper Interlock
12 = Open Safety
13 = Seal Leakage
14 = Valve sequence
15 = Megger Shutdown
16 = High Pump Temp