Datasheet

© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
2
IPC36XX- Front
CB
IPC3601 Rear
IPC3602 Rear
CHASSIS
1.72” (1U) x Depth 9.5” x Width 19.0”
Weighs approximately 12 lbs.
Powder coated black steel
Detachable mounting brackets allow for
several mounting options
NEMA or IEC 320 OUTLETS
IPC3601 has 8 IEC 60320 Type
C13 (computer style) outlets
IPC3602 has 8 NEMA 5-15R
(3 prong) outlets
12 INDICATOR LIGHTS
Main power system on
Power “on” to outlets 1-8
2 Data and ethernet link
POWER INPUT
IEC 60320 Type C20 Inlet
Mating power cables must be
ordered separately
IPC3601 has a full range power
supply for use at 100-240V
EMI/RFI FILTERING
Common Mode - Line to Ground
Differential Mode - Line to Line
Filtered inlet isolates noise before
entering the system
IPC3601-F3-3316 –
NO FILTER
SPIKE/SURGESUPPRESSION
Line to Neutral (or Line)
OVERLOAD PROTECTION
Push button circuit breaker pops out
when an overload occurs
Push to reset
SOFTWARE SECURITY
User name/password security
Settings allow the administrator to
disable unused interfaces
SERIAL/ETHERNET
Serial RS232 via RJ22 connector on the
rear. 6’ RJ22 to DB9 cable included
Serial baud rate is 9600 default or
38,400 maximum
Ethernet (10/100) network via RJ45
connector on the rear. 6’ network
cable included
Network setup allows DHCP or any
static public/private IP address
SOFTWARE INTERFACES
Web interface provides a graphic
control interface through a web
browser (IE, Netscape, Mozilla)
Telnet interface provides a text menu
control interface with any terminal
emulation software
SNMP allows read/write capability
with trapping
E-mail notification system provides e-mail
alerts or logs showing user activity
Serial interface provides a text menu
control interface with any terminal
emulation software
FTP utility allows firmware upgrades
SOFTWARE FEATURES
Administrator and multiple users can
be configured
User level access can be limited to
specific outlets
Unit and outlet names can be configured
Outlet groups can be created to
perform an action on multiple outlets
Outlet control includes individual,
group and all outlet global control
Outlet actions include on or off and reboot
Global sequence allows all the
outlets to be turned on or off in a
preset sequence up to 999 seconds
Outlet reboot automatically turns an outlet
off and back on with one command at a
preset time up to 999 seconds
E-mail notification allows up to two
e-mail addresses to receive notifications
of alerts or events
AUTO-EVENT SCHEDULING
Administrator can configure on or off
events for outlets or groups. The event
occurs at the preset time daily or weekly
SPECIFICATIONS IPC3601 IPC3602 IPC3601-F3-3316
Approvals CB, CE, UL/cUL Listed, FCC UL/cUL Listed, FCC NA
Voltage Input/Output (50/60Hz) 100-240V~ 120V~ 200-240V~
Current Rating
16A 16A 24A
Full Load VA 1920VA @ 120V~
3840VA @ 240V~
1920VA 5760VA
Ethernet/Serial YES YES YES
Outlets IEC C13 NEMA 5-15R IEC C13
Circuit Breaker 20A 20A (2) 15/15A
EMI/RFI Filter 20A 20A
NO
Surge Suppression YES YES YES
Power Input C20 Inlet C20 Inlet Attached
Power Cable/Plug Not Included Not Included 10’ - L6-30P