IQ 250/260 High Performance Multifunction Electricity Meter Installation & Operation Manual IB02601006E Rev. 1.
IQ 250/260 Meter Table of Contents 1 INTRODUCTION About this Manual Warranty and Liability Information Safety Precautions 2 IQ 250/260 Overview and Specifications IQ 250/260 Overview Voltage and Current Inputs Ordering Information Measured Values Utility Peak Demand Specifications Compliance Accuracy 3 Mechanical Installation Introduction ANSI Install
IQ 250/260 Meter 6 Using the IQ 250/260 6-1 Introduction Understanding Meter Face Elements Understanding Meter Face Buttons Using the Front Panel Understanding Startup and Default Displays Using the Main Menu Using Reset Mode Entering a Passwords Using Configuration Mode Configuring the Scroll Feature Configuring CT Setting Configuring PT Setting Configuring Connection Setting
IQ 250/260 Meter 8 Programming the IQ 250/260 8-1 Overview Connecting to the IQ 250/260 Accessing the IQ 250/260 Device Profile Selecting Settings Performing Tasks Configuring Settings Configuring CT, PT Ratios and System Hookup Configuring Time Settings Configuring System Settings Configuring Communications Settings Setting Display Configuration Configuring Energy, Power Scaling, and Averagin
IQ 250/260 Meter Appendix A - IQ 250/260 Navigation Maps Introduction Navigation Maps Appendix B - Modbus Mapping for IQ 250/260 Introduction Modbus Register Map Sections Data Formats Floating Point Values Important Note Concerning IQ 250/260 Modbus Map Retrieving Logs Using the IQ 250/260 with L Option’s Modbus Map Log Retrieval Procedure Log Retrieval Example Log Record Interpretation
IQ 250/260 Meter 1 Chapter 1: Introduction Introduction About This Manual This document is the user manual for the installation, operation, and maintenance of the Eaton IQ 250/260 Meter. It is intended for authorized and qualified personnel who use the IQ 250/260 Meter. Please refer to the specific WARNINGS and CAUTIONS in this section before proceeding.
Chapter 1: Introduction IQ 250/260 Meter Safety Precautions All safety codes, safety standards, and/or regulations must be strictly observed in the installation, operation, and maintenance of this device. WARNINGS refer to instructions that, if not followed, can result in death or injury. CAUTIONS refer to instructions that, if not followed, can result in equipment damage. WARNINGS SHOCK HAZARDS: IMPROPER INSTALLATION CAN CAUSE DEATH, INJURY, AND/OR EQUIPMENT DAMAGE.
Chapter 2: Overview and Specifications IQ 250/260 Meter 2 Overview and Specifications IQ 250/260 Overview The IQ 250/260 is a multifunction power and energy meter designed to be used in electrical substations, panel boards, and as a primary revenue meter, due to its high performance measurement capability.
Chapter 2: Overview and Specifications IQ 250/260 Meter Voltage and Current Inputs Universal Voltage Inputs Voltage Inputs allow measurement up to 480VAC (Phase to Reference) and 600VAC (Phase to Phase). This insures proper meter safety when wiring directly to high voltage systems. One unit will perform to specification on 69 Volt, 120 Volt, 230 Volt, 277 Volt, and 347 Volt power systems. NOTE: Higher voltages require the use of potential transformers (PTs).
IQ 250/260 Meter Chapter 2: Overview and Specifications Ordering Information IQ - 260 - M - A - 6 - 5 - 1 - 1 - 0 1 2 3 4 5 6 7 8 1. Model: 250 = Power Meter 260 = Power Quality Meter 2. Meter Type M = Meter (with integral display) T = Transducer Only (no display) 3. Data Logging: A= None L= On-board data logging 4. Frequency: 5 = 50 Hz System 6 = 60 Hz System 5.
Chapter 2: Overview and Specifications IQ 250/260 Meter Measured Values The IQ 250/260 provides the following Measured Values all in Real-Time Instantaneous, and some additionally as Average, Maximum and Minimum values. IQ 250/260 Measured Values Measured Values Avg 2-4 Instantaneous Max Min Voltage L-N X X X Voltage L-L X X X Current per Phase X X X X Current Neutral X X X X WATT(A,B,C,Tot.) X X X X VAR (A,B,C,Tot.
IQ 250/260 Meter Chapter 2: Overview and Specifications Utility Peak Demand The IQ 250/260 provides user-configured Fixed Window or Sliding Window Demand modes. This feature enables you to set up a customized Demand profile. Fixed Window Demand mode records the average demand for time intervals that you define (usually 5, 15 or 30 minutes). Sliding Window Demand mode functions like multiple, overlapping Fixed Window Demands.
Chapter 2: Overview and Specifications IQ 250/260 Meter KYZ/RS485 Port Specifications RS485 Transceiver; meets or exceeds EIA/TIA-485 Standard: Type: Min. Input Impedance: Max. Output Current: Two-wire, half duplex 96kΩ ±60mA Wh Pulse KYZ output contacts (and infrared LED light pulses through face plate): (See Chapter 6 for Kh values.) Pulse Width: Full Scale Frequency: Contact type: Relay type: Peak switching voltage: Continuous load current: Peak load current: On resistance, max.
IQ 250/260 Meter Chapter 2: Overview and Specifications Isolation All Inputs and Outputs are galvanically isolated to 2500 Vac Environmental Rating Storage: Operating: Humidity: Faceplate Rating: (-20 to +70)0 C (-20 to +70)0 C to 95% RH Non-condensing NEMA12 (Water Resistant), Mounting Gasket Included Measurement Methods Voltage, Current: Power: True RMS Sampling at over 400 Samples per Cycle on All Channels Update Rate Watts, VAR and VA: All other parameters: Every 6 cycles (e.g.
Chapter 2: Overview and Specifications IQ 250/260 Meter Compliance • • • • • I C12.2• UL Listing: USL/CNL E185559 CE Compliant IEC 62053-22(0.2% Accuracy) ANSI C12.20 (0.2% Accuracy)• ANSI C62.41 (Burst)• IEC 1000-4-2 - ESD • ANSI C62.41 to be supplied before document release Accuracy (See full Range specifications earlier in this chapter.
Chapter 3: Mechanical Installation IQ 250/260 Meter 3 Mechanical Installation Introduction The IQ 250/260 meter can be installed using a standard ANSI C39.1 (4” Round) or an IEC 92mm DIN (Square) form. In new installations, simply use existing DIN or ANSI punches. For existing panels, pull out old analog meters and replace them with the IQ 250/260. The various models use the same installation. See Chapter 4 for wiring diagrams.
2.32] 5.02 [12.75] Chapter 3: Mechanical Installation IQ 250/260 Meter 0.77 [1.95] 3.25 [8.26] 0.95 [2.41] 3.56 [9.04] 4.85 [12.32] 0.91 [2.31] 3.56 [9.04] Fig. 3.4: IQ 250/260 Back Face Figure 3.5: ANSI Mounting Panel Cutout Figure 3.6: DIN Mounting Cutout 3-2 IB02601006E 3.25 [8.26] www.eaton.com 0.77 [1.
IQ 250/260 Meter Chapter 3: Mechanical Installation ANSI Installation Steps NEMA 12 Mounting Gasket Threaded Rods Lock Washer and Nut Figure 3.7: ANSI Mounting Procedure 1. 2. 3. 4. Insert 4 threaded rods by hand into the back of meter. Twist until secure. Slide NEMA 12 Mounting Gasket onto back of meter with rods in place. Slide meter with Mounting Gasket into panel. Secure from back of panel with lock washer and nut on each threaded rod. Use a small wrench to tighten. Do not overtighten.
Chapter 3: Mechanical Installation IQ 250/260 Meter DIN Installation Steps DIN Mounting Bracket (supplied by others: if needed, contact technical support referenced on page 1-1) Top Mounting Bracket Groove Bottom Mounting Bracket Groove #8 Screw IQ 250/260 Meter with NEMA 12 Mounting Gasket Remove (unscrew) ANSI Studs for DIN Installation Figure 3.8: DIN Mounting Procedure 1. Slide meter with NEMA 12 Mounting Gasket into panel. (Remove ANSI Studs, if in place.) 2.
IQ 250/260 Meter Chapter 3: Mechanical Installation IQ 250/260T Transducer Installation The IQ 250/260T Transducer model is installed using DIN Rail Mounting. Specs for DIN Rail Mounting: DIN Rail (Slotted) Dimensions: International Standards DIN 46277/3 0.297244” x 1.377953” x 3” (inches) 7.55mm x 35mm x 76.2mm (millimeters) Release Clip Figure 3.9: DIN Rail Mounting Procedure Release Clip 1. Slide top groove of meter onto the DIN Rail. 2. Press gently until the meter clicks into place.
Chapter 3: Mechanical Installation 3-6 IQ 250/260 Meter IB02601006E www.eaton.
IQ 250/260 Meter 4 Chapter 4: Electrical Installation Electrical Installation Considerations When Installing Meters Installation of the IQ 250/260 Meter must be performed only by qualified personnel who follow standard safety precautions during all procedures. Those personnel should have appropriate training and experience with high voltage devices. Appropriate safety gloves, safety glasses and protective clothing is recommended.
Chapter 4: Electrical Installation IQ 250/260 Meter CT Leads Terminated to Meter The IQ 250/260 is designed to have Current Inputs wired in one of three ways. Diagram 4.1 shows the most typical connection where CT Leads are terminated to the meter at the Current Gills. This connection uses Nickel-Plated Brass Studs (Current Gills) with screws at each end. This connection allows the CT wires to be terminated using either an “O” or a “U” lug. Tighten the screws with a #2 Phillips screwdriver.
Chapter 4: Electrical Installation IQ 250/260 Meter CT Leads Pass Through (No Meter Termination) The second method allows the CT wires to pass through the CT Inputs without terminating at the meter. In this case, remove the Current Gills and place the CT wire directly through the CT opening. The opening will accomodate up to 0.177” / 4.5mm maximum diameter CT wire. CT Wire passing through meter Current Gills removed Figure 4.2: Pass-Through Wire Electrical Connection www.eaton.
Chapter 4: Electrical Installation IQ 250/260 Meter Quick Connect Crimp-on Terminations For Quick Termination or for Portable Applications, a 0.25” Quick Connect Crimp-on Connectors can also be used. Quick Connect Crimp-on Terminations Figure 4.3: Quick Connect Electrical Connection 4-4 IB2601006E www.eaton.
IQ 250/260 Meter Chapter 4: Electrical Installation Voltage and Power Supply Connections Voltage Inputs are connected to the back of the unit via a optional wire connectors. The connectors accomodate AWG# 12 -26/ (0.129 - 3.31)mm2. RS485 and KYZ Pulse Output CAUTION! Do not apply input or supply voltage to these terminals. Power Supply Inputs Voltage Inputs Figure 4.
Chapter 4: Electrical Installation IQ 250/260 Meter Electrical Connection Diagrams The following pages contain electrical connection diagrams for the IQ 250/260 meter. Choose the diagram that best suits your application. Be sure to maintain the CT polarity when wiring. The diagrams are presented in the following order: 1. Three Phase, Four-Wire System Wye/Delta with Direct Voltage, 3 Element a. Example of Dual Phase Hookup b. Example of Single Phase Hookup 2.
Chapter 4: Electrical Installation IQ 250/260 Meter 1. Service: WYE/Delta, 4-Wire with No PTs, 3 CTs C Select: “ 3 EL WYE ” (3 Element Wye) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) C A B www.eaton.
Chapter 4: Electrical Installation IQ 250/260 Meter 1a. Example of Dual Phase Hookup 4-8 IB2601006E www.eaton.
IQ 250/260 Meter Chapter 4: Electrical Installation 1b. Example of Single Phase Hookup www.eaton.
Chapter 4: Electrical Installation IQ 250/260 Meter 2. Service: 2.5 Element WYE, 4-Wire with No PTs, 3 CTs C A Select: “ 2.5 EL WYE ” (2.5 Element Wye) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) 4-10 IB2601006E B www.eaton.
Chapter 4: Electrical Installation IQ 250/260 Meter 3. Service: WYE/Delta, 4-Wire with 3 PTs, 3 CTs C C C A Select: “ 3 EL WYE ” (3 Element Wye) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) B www.eaton.
Chapter 4: Electrical Installation IQ 250/260 Meter 4. Service: 2.5 Element WYE, 4-Wire with 2 PTs, 3 CTs C A Select: “ 2.5 EL WYE ” (2.5 Element Wye) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) 4-12 IB2601006E B www.eaton.
IQ 250/260 Meter Chapter 4: Electrical Installation 5. Service: Delta, 3-Wire with No PTs, 2 CTs C C B Select: “ 2 Ct dEL ” (2 CT Delta) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) www.eaton.
Chapter 4: Electrical Installation IQ 250/260 Meter 6. Service: Delta, 3-Wire with 2 PTs, 2 CTs C C A B B Select: “ 2 Ct dEL ” (2 CT Delta) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) 4-14 IB2601006E Not connected to meter www.eaton.
IQ 250/260 Meter Chapter 4: Electrical Installation 7. Service: Delta, 3-Wire with 2 PTs, 3 CTs C C B Select: “ 2 Ct dEL ” (2 CT Delta) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) A B A Not connected to meter NOTE: The third CT for hookup is optional and is for Current Measurement only. www.eaton.
Chapter 4: Electrical Installation IQ 250/260 Meter 8. Service: Current Only Measurement (Three Phase) * Select: “ 3 EL WYE ” (3 Element Wye) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) * For improved accuracy, this connection is recommended, but not required. 4-16 IB2601006E www.eaton.
IQ 250/260 Meter Chapter 4: Electrical Installation 9. Service: Current Only Measurement (Dual Phase) * Select: “ 3 EL WYE ” (3 Element Wye) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) * For improved accuracy, this connection is recommended, but not required. www.eaton.
Chapter 4: Electrical Installation IQ 250/260 Meter 10. Service: Current Only Measurement (Single Phase) * Select: “ 3 EL WYE ” (3 Element Wye) from the IQ 250/260’s Front Panel Display. (See Chapter 6.) * For improved accuracy, this connection is recommended, but not required. 4-18 IB2601006E www.eaton.
IQ 250/260 Meter 5 Chapter 5: Communication Installation Communication Installation IQ 250/260 Communication The IQ 250/260 Meter provides RS485 communication speaking Modbus ASCII, Modbus RTU, and DNP 3.0 protocols. RS485 / KYZ Output (Com 2) Com 2 provides a combination RS485 and an Energy Pulse Output (KYZ pulse). See Chapter 2 for the KYZ Output Specifications; see Chapter 6 for Pulse Constants. Figure 5.
Chapter 5: Communication Installation IQ 250/260 Meter Figure 5.2 shows the detail of a 2-wire RS485 connection. IQ 250/260 485 Connection Figure 5.2: 2-wire RS485 Connection NOTES: For All RS485 Connections: • Use a shielded twisted pair cable 22 AWG (0.33 mm2) or thicker, and ground the shield, preferably at one location only. • Establish point-to-point configurations for each device on a RS485 bus: connect (+) terminals to (+) terminals; connect (-) terminals to (-) terminals.
Chapter 5: Communication Installation IQ 250/260 Meter Slave device 1 SH + - Long stub results “T” connection that can cause interference problem! Master device Last Slave device N RT RT Slave device 2 SH + - SH Twisted pair, shielded (SH) cable + - SH Twisted pair, shielded (SH) cable + - Twisted pair, shielded (SH) cable Earth Connection, preferably at single location Twisted pair, shielded (SH) cable Twisted pair, shielded (SH) cable Slave device 1 Slave device 2 SH + - Master d
Chapter 5: Communication Installation IQ 250/260 Meter Using the Power Xpert® Gateway The Power Xpert® Gateway allows an IQ 250/260 to communicate with a PC through a standard web browser. See the Power Xpert ®Gateway User Guide, document number 164201670, for additional information. IQ 250/260T Communication Information The IQ 250/260T Transducer model does not include a display or buttons on the front face of the meter.
IQ 250/260 Meter 6 Chapter 6: Using the IQ 250/260 Using the IQ 250/260 Introduction You can use the Elements and Buttons on the IQ 250/260 meter’s face to view meter readings, reset and/or configure the IQ 250/260, and perform related functions. The following sections explain the Elements and Buttons and detail their use.
Chapter 6: Using the IQ 250/260 IQ 250/260 Meter Using the Front Panel You can access four modes using the IQ 250/260 front panel buttons: • Operating Mode (Default) • Reset Mode • Configuration Mode • Information Mode. Information Mode displays a sequence of screens that show model information, such as Frequency and Amps. Use the Menu, Enter, Down and Right buttons to navigate through each mode and its related screens.
IQ 250/260 Meter Chapter 6: Using the IQ 250/260 Using the Main Menu 1. Press the Menu button. The Main Menu screen appears. • The Reset: Demand mode (rStd) appears in the A window. Use the Down button to scroll, causing the Reset: Energy (rStE), Configuration (CFG), Operating (OPr), and Information (InFo) modes to move to the A window. • The mode that is currently flashing in the A window is the “Active” mode, which means it is the mode that can be configured.
Chapter 6: Using the IQ 250/260 IQ 250/260 Meter Entering a Password If Password Protection has been enabled in the software for Reset and/or Configuration (see Chapter 8 for information), a screen appears requesting a Password when you try to reset the meter and/or configure settings through the front panel. • PASS appears in the A window and 4 dashes appear in the B window. The leftmost dash is flashing. 1. Press the Down button to scroll numbers from 0 to 9 for the flashing dash.
IQ 250/260 Meter Chapter 6: Using the IQ 250/260 Using Configuration Mode Configuration Mode follows Reset: Energy on the Main Menu. To access Configuration Mode: 1. Press the Menu button while the meter is auto-scrolling parameters. 2. Press the Down button until the Configuration Mode option (CFG) is in the A window. 3. Press the Enter button. The Configuration Parameters screen appears. 4.
Chapter 6: Using the IQ 250/260 IQ 250/260 Meter Configuring the Scroll Feature When in Auto Scroll mode, the meter performs a scrolling display, showing each parameter for 7 seconds, with a 1 second pause between parameters. The parameters that the meter displays are determined by the following conditions: • They have been selected through software. (Refer to Chapter 8 for instructions.) • Whether your meter model is an IQ 250 or IQ 260. To enable or disable Auto-scrolling: 1.
Chapter 6: Using the IQ 250/260 IQ 250/260 Meter Configuring CT Setting The CT Setting has three parts: Ct-n (numerator), Ct-d (denominator), and Ct-S (scaling). 1. Press the Enter button when Ct is in the A window. The Ct-n screen appears. You can either: • Change the value for the CT numerator. • Access one of the other CT screens by pressing the Enter button: press Enter once to access the Ct-d screen, twice to access the Ct-S screen.
Chapter 6: Using the IQ 250/260 IQ 250/260 Meter Configuring PT Setting The PT Setting has three parts: Pt-n (numerator), Pt-d (denominator), and Pt-S (scaling). 1. Press the Enter button when Pt is in the A window. The PT-n screen appears. You can either: • Change the value for the PT numerator. • Access one of the other PT screens by pressing the Enter button: press Enter once to access the Pt-d screen, twice to access the Pt-S screen. a.
IQ 250/260 Meter Chapter 6: Using the IQ 250/260 Configuring Connection Setting 1. Press the Enter button when Cnct is in the A window. The Cnct screen appears. 2. Press the Right button or Down button to select a configuration. The choices are: • 3 Element Wye (3 EL WYE) • 2.5 Element Wye (2.5EL WYE) • 2 CT Delta (2 Ct dEL) NOTE: If you are prompted to enter a password, refer to the instructions earlier in this chapter. 3.
Chapter 6: Using the IQ 250/260 IQ 250/260 Meter Using Operating Mode Operating Mode is the IQ 250/260 meter’s default mode, that is, the standard front panel display. After Startup, the meter automatically scrolls through the parameter screens, if scrolling is enabled. Each parameter is shown for 7 seconds, with a 1 second pause between parameters. Scrolling is suspended for 3 minutes after any button is pressed. 1. Press the Down button to scroll all the parameters in Operating Mode.
IQ 250/260 Meter Chapter 6: Using the IQ 250/260 Understanding the % of Load Bar The 10-segment LED bar graph at the bottom left of the IQ 250/260 front panel provides a graphic representation of Amps. The segments light according to the load, as shown in the % Load Segment Table below. When the Load is over 120% of Full Load, all segments flash “On” (1.5 secs) and “Off” (0.5 secs).
Chapter 6: Using the IQ 250/260 IQ 250/260 Meter Performing Watt-Hour Accuracy Testing (Verification) To be certified for revenue metering, power providers and utility companies must verify that the billing energy meter performs to the stated accuracy. To confirm the meter’s performance and calibration, power providers use field test standards to ensure that the unit’s energy measurements are correct.
IQ 250/260 Meter 7 Chapter 7: Using the I/O Option Cards Using the I/O Option Cards Overview The IQ 250/260 offers extensive I/O expandability. Using the two universal Option Card slots, the unit can be easily configured to accept new I/O Option cards even after installation, without your needing to remove it from the installation. The IQ 250/260 auto-detects any installed Option cards. Up to 2 modules of any type outlined in this chapter can be used per meter.
Chapter 7: Using the I/O Option Cards IQ 250/260 Meter Installing Option Cards The Option Cards are inserted in one of the two Option Card slots in the back of the IQ 250/260. Note: Remove Voltage Inputs and power supply terminal to the IQ 250/260 before performing card installation. 1. Remove the screws at the top and the bottom of the Option Card slot covers. 2. There is a plastic “track” on the top and the bottom of the slot. The Option card fits into this track.
IQ 250/260 Meter Chapter 7: Using the I/O Option Cards The following sections describe the available Option cards. Digital Output (Relay Contact) / Digital Input Card (IQ250/260-IO1) The Digital Output/Input card is a combination of relay contact outputs for load switching and dry/wet contact sensing digital inputs. The outputs are electrically isolated from the inputs and from the main unit. Specifications The technical specifications at 25 °C are as follows: Power consumption: 0.
Chapter 7: Using the I/O Option Cards IQ 250/260 Meter Wiring Diagram Relay card Fig. 7.3: Relay Contact (2) / Status Input (2) Card Pulse card 7-4 IB02601006E www.eaton.
IQ 250/260 Meter Chapter 7: Using the I/O Option Cards Pulse Output (Solid State Relay Contacts) / Digital Input Card (IQ250/260-IO2) The Pulse Output/Digital Input card is a combination of pulse outputs via solid state contacts and dry/wet contact sensing digital inputs. The outputs are electrically isolated from the inputs and from the main unit. Specifications The technical specifications at 25 °C are as follows: Power consumption: 0.
Chapter 7: Using the I/O Option Cards IQ 250/260 Meter Wiring Diagram Relay card Pulse card 7-6 IB02601006E Fig. 7.4: Pulse Output (4) / Status Input (4) Card www.eaton.
IQ 250/260 Meter Chapter 7: Using the I/O Option Cards 1mA Output Card (IQ250/260-IO3) The 1mA card transmits a standardized bi-directional 0-1mA signal. This signal is linearly proportional to real-time quantities measured by the IQ 250/260 meter. The outputs are electrically isolated from the main unit. Specifications: The technical specifications at 25° C at 5kΩ load are as follows: Number of outputs: Power consumption: Signal output range: Max.
Chapter 7: Using the I/O Option Cards IQ 250/260 Meter Wiring Diagram 0-1mA Fig 7.5: 4-Channel 0 - 1mA Output Card 0-20mA 7-8 IB02601006E www.eaton.
IQ 250/260 Meter Chapter 7: Using the I/O Option Cards 20mA Output Card (IQ250/260-IO4) The 20mA card transmits a standardized 0-20 mA signal. This signal is linearly proportional to real-time quantities measured by the IQ 250/260. The current sources need to be loop powered. The outputs are electrically isolated from the main unit. Specifications The technical specifications at 25° C at 500Ω load are as follows: Number of outputs: Power consumption: Signal output range: Max.
Chapter 7: Using the I/O Option Cards IQ 250/260 Meter Wiring Diagram 0-1mA 0-20mA Fig. 7.6: 4-Channel 4 - 20mA Output Card 7-10 IB02601006E www.eaton.
IQ 250/260 Meter 8 Chapter 8: Programming the IQ 250/260 Programming the IQ 250/260 Overview The IQ 250/260 Meter can be configured using either the meter Face Buttons (Menu, Enter, Down and Right) or Eaton Meter Configuration Software. To connect to the meter for software configuration, use the RS485 port (Com 2) on the back panel of the meter. The 250/260T must be configured with the Eaton Meter Configuration Software, using the RS485 port, since it does not have a front panel.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Accessing the IQ 250/260 Device Profile 1. Click the Profile icon in the Title Bar. You will see the IQ 250/260 Device Profile screen. The Menu on the left side of the screen allows you to navigate between settings screens (see below). The Device Profile screen features a Tree Menu for Settings navigation, and Buttons and a Title Bar that allow you to perform tasks, for example, updating the Device Profile.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 Performing Tasks You can perform tasks from either the Device Profile screen Buttons or from the Title Bar. n The screen Buttons and their functions are as follows: · Update Device: Click to send the current settings to the meter. NOTE: You must click the Update Device button after making changes to the Settings screens, if you want to update the connected meter’s settings. · Save Profile: Click to save the Device Profile settings to a file.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter n Three items in the Title Bar - File, Tools, and View - open menus that allow you to perform functions. These menus and functions are described below. When you click User Manual from the Title Bar a pdf file of this manual opens, with instructions for whichever Device Profile Setting is active at the current time.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 · Click View from the Title Bar to see the menu shown on the right. The View menu allows you to: o View Output Logs/Errors: View the Errors Log. o View Last Update Information: View Update information for this Device Profile. NOTE: The instructions for these two functions follow.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Configuring Settings The following sections contain detailed instructions for configuring the Device Profile settings. All of the settings are reached from the Tree Menu of the Device Profile screen. Configuring CT, PT Ratios and System Hookup Use this setting to configure Current Transformer and Potential Transformer ratios and to select the System Hookup.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 For a system that has 14400V primary with a 120V secondary line to neutral (PT Ratio of 120:1), set the following PT Ratios in the entry fields: PT Numerator (Primary) 1440 PT Denominator (Secondary 120 PT Multiplier 10 The Voltage Full Scale field will read 14400. Configuring Time Settings Use this setting to enable or disable Daylight Savings Time for the IQ 250/260, and to set the beginning and ending times for Daylight Savings Time.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter When you click the Change button next to Change Password in the Settings screen, you will see the Enter the New Password screen. 1. Type in the new password (0 - 9999). 2. Retype the password. 3. Click Change. The new password will be saved and the meter will restart.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 NOTE: Response Delay is the delay the meter should use before responding to queries. If your connecting device requires a delay before receiving information, use response delay to program the time to wait before the meter starts responding to queries. Setting Display Configuration Use this screen to set the display of the meter’s faceplate. Refer to Chapter 6 of this manual for additional information and instructions on using the faceplate.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Configuring Energy, Power Scaling, and Averaging Use this setting to configure: • The display of Power in the meter • The display and storage of Energy in the meter • The interval over which Average values are computed.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 From the Tree Menu, click Energy Settings> Energy, Power Scaling, and Averaging. The screen fields and acceptable entries are as follows: • Energy Settings Energy Digits: 5; 6; 7; 8 Energy Decimal Places: 0 - 6 Energy Scale: unit; kilo (K); Mega (M) For example: a reading for Digits: 8; Decimals: 3; Scale: K would be formatted: 00123.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Configuring Limits (IQ 260 Only) Use this screen to assign Limits for the meter. v Functional Overview for Limits: Limits are transition points used to divide acceptable and unacceptable measurements. When a value goes above or below the limit, an out-of-limit condition occurs. You can set and configure up to eight Limits for the IQ 260 meter. Once they are configured, you can view the out-of-Limits (or Alarm) conditions in the Limits Polling screen.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 To Configure a Limit: Double-click on the Field to set the following values: Above and Below Set Point: % of Full Scale (the point at which the reading goes out of limit) Examples: 100% of 120V Full Scale = 120V 90% of 120V Full Scale = 108V Above and Below Return Hysteresis: (the point at which the reading goes back within limit) Examples: Above Set Point = 110% Below Set Point = 90% (Out of Limit above 132V) (Out of Limit below 108V) Above Ret
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Configuring Trending Profile (Data logging option) If your meter has the data logging option (see Chapter 2) you will see the Trending Profiles setting in the Tree Menu. Click on Trending Profiles>Historical Log Profile 1 to display the screen shown below. (The screen shown here is for an IQ 260 meter with the L option. If you are connected to an IQ250 with the L option, you won’t see the Power Quality and Alarm menu options.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 NOTES: • Only one Option Card input or output can be set to trigger an EOI pulse. • The maximum rate for EOI Pulse used to trigger a log is once per minute. • When you choose EOI Pulse, the meter takes a snapshot on the End of Interval Pulse condition, rather than on a time interval. Below are two examples of using EOI Pulse for log recording.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter The Time Range Retrieval mode is useful if you want to retrieve specific events. If you select Use Time Range from the pull-down menu, date range fields will display, allowing you to select the time range for data retrieval. Only records (within the specified time range) that are newer than the latest records in the log database can be retrieved for any selected logs.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 1. Choose the log data file(s) you want to view in either of the following ways: • • If you have retrieved logs through Eaton Meter Configuration Software, the meter’s designated label is shown in the field above the Meter 1 button. Click the Log’s button on the right side of the screen to view a log. (The buttons of unavailable logs are grayed out and unselectable.) If you want to view a previously retrieved log, click either Meter button (1 or 2).
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter 4. From the Available Data Points column, click on the data points you want to include when viewing the log file. To select multiple points, hold down the Ctrl key while clicking. To select points in sequence, hold down the Shift key while clicking. • • Click the Add button to move the Data Points to the Selected Data Points column. Click the Restore button to return the selection to its previous setting. 5.
IQ 250/260 Meter • • • • Chapter 8: Programming the IQ 250/260 The name of the log file and the type of data point are listed in the top row. You can move the columns, so that the most important data is most accessible. Right-click on the column title and drag it to the desired location on the table. To save the data to your clipboard, right-click with the cursor positioned anywhere in the table.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter 9. To display Trending data as either an XY, Circular, or Advanced graph, click the Graph button. You will see the following screen. The Available Items column lists the log’s data points. (To add a new data point, return to Log Viewer’s main screen and click the Data Points button.) a. Click on the data points you want to graph. b. Click the Add button. The items appear in the Graph Items column.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 Circular Graph XY Graph www.eaton.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Advanced Graph The following instructions pertain to all of the graphs: • • • • • • • • • • To change the starting point of the graph, choose a new date/time segment from the Starting Date/Time to View pull-down menu. To change the amount of time represented on the graph, enter a value in the Number of Days to View field and press Enter or click on the Redraw button.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 NOTES: - The Advanced Graph also has a Color button which opens the Color Assignments screen. - The Color Assignments screen is slightly different for the Advanced Graph. The small squares under the Color heading represent the color currently assigned to each component of the graph. To make adjustments to an Item’s color, click the radio button beside it and create a new color by moving the red, green and blue sliders.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Configuring I/O Option Cards The IQ 250/260 Meter automatically detects the presence of any Option cards installed in it. You will see the installed card(s) listed in the Tree Menu (see figure below). Up to two Option cards can be installed in the meter. Refer to Chapter 7 of this manual for additional information concerning Option cards, including installation procedures. You must configure an Option card before using it.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 Configuring a Relay Output/Digital Input Card (IQ250/260-IO1): The Relay Output/Digital Input Option Card has: · Two relay contact outputs for load switching · Two wet/dry contact sensing digital inputs. Accumulators in the software count the transitions of the Inputs and Outputs. For technical specifications and hardware installation, refer to Chapter 7 of this manual.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter 4. You can specify an Accumulation Compression Factor. The Compression Factor is used to adjust how high an accumulator will go before rolling over. Because of this, it is useful in delaying rollover. For example, if you select a Compression Factor of 10, each time 10 Pulse/State changes occur, the accumulator count will increment by 1. The available Compression Factors are: 1, 10, 100, 1000, 10000, and 100000. The default Compression Factor is 1. 5.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 c. Enter Compression. The Compression Factor is used to adjust how high an accumulator will go before rolling over. For example, if you select a Compression Factor of 10, each time 10 Pulse/State changes occur, the accumulator count will increment by 1. The available Compression Factors are: 1, 10, 100, 1000, 10000, and 100000. The default Compression Factor is 1. d. Enter a Label for the Accumulator. e.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter 2. Double-click an Assigned Channel field to add or edit an Output ID. You will see the window shown on the right. 3. Select the Counter Type. The available selections are: • Energy, All Phases • End of Interval Event – this counter is triggered by a Demand Averaging Interval • Energy, Phase A • Energy, Phase B • Energy, Phase C • None. NOTE: If you select one of the Energy Counter Types, you will see the Energy Counter field, shown on the right.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 b. Enter Units/Count. The Units/Count is the output ratio from the device that is being input into the meter. For example, if you have a KYZ module that is outputting a pulse every 1.8 kWh, with the input set to Accumulator, Increment on Contact Opening, you would set the Units/Count to be the value of the KYZ; in this case either 1.8 or a ratio of that number.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter 3. Select Group for your Output Channel. The available selections are as follows: • Readings • Demand • Maximums • Minimums • Phase Angles • THD • Not Assigned. 4. Select Item for your Output Channel. The items are the available readings for the group you selected. For example, as shown in the window above, Volts A-N is an item you can select when you have selected Readings as the Group. 5. Click OK.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 Polling the IQ 250/260 Meter n The Real Time Poll features of the Eaton Meter Configuration Software are used to continuously view instantaneous values within an IQ 250/260 Meter. The software provides tabular views of metered values, circuit measurements, interval data, Power Quality values, Pulse data and Input/Output status and accumulations.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Instantaneous Polling n Click Real-Time Poll>Real Time Readings>Instantaneous Polling. You will see the screen shown below. NOTE: You will only see the THD Readings if you are connected to an IQ 260. n Click Print to print a copy of the screen. n Click Help to view instructions for this screen. n Click OK to return to the main screen. 8-32 IB02601006E www.eaton.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 Poll Max and Min Readings Click Real-Time Poll>Real Time Readings>Poll Max and Min Readings. You will see the screen shown below. This screen displays the maximum and minimum values and the time of their occurrence for all of the IQ 250/260 Real-Time readings. Use the scroll bar to view readings not displayed on the screen. n Click Copy to copy the readings to the clipboard. You can then paste them into another document, for example, an Excel file.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Poll Power and Energy n Click Real-Time Poll>Revenue, Energy and Demand Readings>Power and Energy. You will see the screen shown below. This screen displays the power and energy for Total Power and all three phases. 1. • • • • Click the tabs at the top of the screen to select the view you want: Total Phase A Phase B Phase C 2. Click Print to print the readings. 3. Click OK to close the screen.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 Poll Phasors 1. Click Real Time Poll>Power Quality and Alarms>Phasors. You will see the screen shown below. The Phasors screen displays the Phase relationships of the currently connected IQ 250/260. If you have an auxiliary voltage reading (i.e. generator and bus where the V Aux is the generator), Aux box and the V Aux phaser are displayed. The V Aux phasor is referenced to V A phase. 2.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Poll Status Inputs 1. Click Real Time Poll>Power Quality and Alarms>Poll Status Inputs. You will see the screen shown below. This screen displays the status (Open or Closed) of the Digital Inputs of any installed Relay Output/Digital Input or Pulse Output/Digital Input Option cards. 2. Click Close to close the screen. 8-36 IB02601006E www.eaton.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 Poll Limits (IQ 260 Only) Click Real-Time Poll>Power Quality and Alarms>Limits. You will see the screen shown below. This screen shows the current status of any Limits programmed in the Device Profile. NOTE: See instructions for configuring Limits, earlier in this chapter. 1. The displayed fields are: • Limit ID – the identification of the limit. • Label - the item the Limit is set for. • Value – the current reading for this item.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Using the IQ 250/260 Tools Menu The Tools Menu allows you to access specific functions for the IQ 250/260 Meter. Click Tools from the Title Bar to display the Tools Menu. Accessing the Device Profile Screen Click the first option, Edit Current Device Profile, to open the Device Profile screen. This menu option performs the same function as clicking the Profile icon in the Title Bar. Setting Device Time 1. Click Tools>Set Device Time.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 Resetting Device Information 1. Click Tools>Reset Device Information. You will see the screen shown on the right. 2. Select the items you want to reset and click Reset. NOTES: • You can reset Max/Min Blocks, Energy Accumulators, and Option Card Accumulators. • When installing a Pulse Output/Digital Input card or a Relay Output/Digital Input card, we recommend you reset the accumulators for the card, in order to prevent erroneous counts.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Performing Manual Relay Control 1. Click Tools>Relay Control. You will see the screen shown on the right. This screen allows you to manually set the state of any installed Relay Output/Digital Input cards. 2. The screen displays the current Relay state. To change the state: a. Select the state you want in the Select New State field. b. Click the checkbox next to the Relays you want to change to the new state. c. Click Apply.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 Performing Additional Tasks with Eaton Meter Configuration Software The following sections contain instructions for other tasks you can perform with the Eaton Meter Configuration Software. Using Connection Manager Use Connection Manager to Add or Remove Connection Locations and/or Devices at Locations. 1. Click Connection>Connection Manager or click on the Connect Mgr icon. You will see the screen, shown on the right.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter f. To Edit a Device: - Select the Device from the Devices at Location box. (Scroll down to find all devices.) - Click Edit. You will see the Connection Manager Location Device Editor screen, shown on the right. - Use this screen to program the Device Properties for each device at a Location. • If the Device has a Serial Port Device Connection, you will see the first (top) example screen.
IQ 250/260 Meter Chapter 8: Programming the IQ 250/260 • To Connect to a Location: a. Select the Location you want to connect to from the List of Locations box. NOTE: You may only connect to one location at a time. To change to a different location, you must disconnect from the current location by selecting it and clicking Disconnect. b. Click Connect. When the connection is made, the selected location appears in the Connected To Locations section of the screen. c. Click Close.
Chapter 8: Programming the IQ 250/260 IQ 250/260 Meter Using the Options Screen 1. Click View>Options. You will see the screen shown on the right. Use this screen to access the following features: • Paths for Eaton Meter Configuration Software files • Data Scan Mode • Tech Mode Settings Use the tabs at the top of the screen to access the features. 2. The first Options screen is the Paths screen, shown on the right.
IQ 250/260 Meter App. A Appendix A: IQ 250/260 Navigation Maps IQ 250/260 Navigation Maps Introduction You can configure the IQ 250/260 and perform related tasks using the buttons on the meter face. • Chapter 6 contains a decription of the buttons on the meter face and instructions for programming the meter using them. • The meter can also be programmed using software. See Chapter 8 for instructions on programming the meter using the Eaton Meter Configuration Software.
Appendix A: IQ 250/260 Navigation Maps IQ 250/260 Meter Main Menu Screens (Sheet 1) A-2 IB02601006E www.eaton.
IQ 250/260 Meter Appendix A: IQ 250/260 Navigation Maps Operating Mode Screens (Sheet 2) www.eaton.
Appendix A: IQ 250/260 Navigation Maps IQ 250/260 Meter Reset Mode Screens (Sheet 3) A-4 IB02601006E www.eaton.
Appendix A: IQ 250/260 Navigation Maps IQ 250/260 Meter Configuration Mode Screens (Sheet 4) www.eaton.
Appendix A: IQ 250/260 Navigation Maps A-6 IB02601006E IQ 250/260 Meter www.eaton.
IQ 250/260 Meter App.B Appendix B: IQ 250/260 Modbus Map IQ 250/260 Modbus Map Introduction The Modbus Map for the IQ 250/260 Meter gives details and information about the possible readings of the meter and its programming. The IQ 250/260 can be programmed using the buttons on the face of the meter (Chapter 6) or with the Eaton Meter Configuration Software (Chapter 8).
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter Floating Point Values Floating Point Values are represented in the following format: Register 0 Byte 1 0 1 Bit 7 6 5 4 3 2 1 0 7 6 5 Meaning s e e e e e e e e m m m sign 4 0 0 7 6 5 1 3 2 1 4 3 2 1 0 7 6 5 4 3 2 1 0 m m m m m m m m m m m m mm m m m m mm exponent mantissa sign exponent-127 The formula to interpret a Floating Point Value is: -1 x2 x1.
IQ 250/260 Meter Appendix B: IQ 250/260 Modbus Map Important Note Concerning the IQ 250/260 Meter’s Modbus Map In depicting Modbus Registers (Addresses), the IQ 250/260 meter’s Modbus map uses Holding Registers only. Hex Representation The representation shown in the table below is used by developers of Modbus drivers and libraries, SEL 2020/2030 programmers and Firmware Developers. The IQ 250/260 meter’s Modbus map also uses this representation.
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter Retrieving Logs Using the IQ 250/260 Meter with Option L’s Modbus Map This section describes the log interface system of the IQ 250/260 meters with the logging option from a programming point of view. It is intended for Programmers implementing independent drivers for Log Retrieval from the meter.
Appendix B: IQ 250/260 Modbus Map IQ 250/260 Meter Block Definitions This section describes the Modbus Registers involved in retrieving and interpreting an IQ 250/260 meter’s log. Other sections refer to certain ‘values’ contained in this section. See the corresponding value in this section for details. NOTES: Register is the Modbus Register Address in 0-based Hexadecimal notation. To convert it to 1based decimal notation, convert from hex16 to decimal10 and add 1. For example: 0x03E7 = 1000.
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter 0x01 1 minute 0x02 3 minute 0x04 5 minute 0x08 10 minute 0x10 15 minute 0x20 30 minute 0x40 60 minute End of Interval (EOI) Pulse: Setting the interval to EOI causes a record to be logged whenever an EOI pulse event is generated. This is most commonly used in conjunction with the Digital I/O Option Cards. 0 NOTE: The interval between records will not be even (fixed), and thus should not be used with programs that expect a fixed interval. ii.
Appendix B: IQ 250/260 Modbus Map IQ 250/260 Meter 5 6 Unsigned Integer Signed Integer 0.1 scale: Special Signed Integer, where the value is divided by 10 to give a 0.1 scale. Unused Disabled: used as end list marker. 7-14 15 Size: The size in bytes of the item described. This number is used to determine the pairing of descriptors with register items.
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter NOTE: The first record in every log before it has rolled over is a “dummy” record, filled with all 0xFF’s. When the log is filled and rolls over, this record is overwritten. Record Size: The number of bytes in this record, including the timestamp. The data type is an unsigned integer in the range of 14 – 242. Log Availability: A flag indicating if the log is available for retrieval, or if it is in use by another port.
IQ 250/260 Meter Appendix B: IQ 250/260 Modbus Map To get the current Com Port, see the NOTE on querying the port, on the previous page. i. The Log Retrieval Header is used to program the log to be retrieved, the record(s) of that log to be accessed, and other settings concerning the log retrieval.
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter For example, with a record size of 30, the RecPerWindow = ((123 x 2) \ 30) = 8.2 ~= 8 Number of Repeats: Specifies the number of repeats to use for the Modbus Function Code 0x23 (35) (See next page for more information on this Function Code). Since the meter must pre-build the response to each log window request, this value must be set once, and each request must use the same repeat count.
IQ 250/260 Meter Appendix B: IQ 250/260 Modbus Map Log Retrieval Log Retrieval is accomplished in 3 basic steps: 1. 2. 3. Engage the log. Retrieve each of the records. Disengage the log. Auto-Increment In the traditional Modbus retrieval system, you write the index of the block of data to retrieve, then read that data from a buffer (window). To improve the speed of retrieval, the index can be automatically incremented each time the buffer is read.
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter Log Retrieval Procedure The following procedure documents how to retrieve a single log from the oldest record to the newest record, using the “normal” record type (see Scope). All logs are retrieved using the same method. See following section for a Log Retrieval example. NOTES: This example uses auto-increment. In this example, Function Code 0x23 is not used You will find referenced topics in the Block Definitions section.
IQ 250/260 Meter Appendix B: IQ 250/260 Modbus Map Space in the window after the last specified record (RecordSize x RecordPerWindow) is padded with 0xFF, and can be safely discarded. b) Verify that the record index incremented by Records Per Window. The record index of the retrieved window is the index of the first record in the window. This value will increase by Records Per Window each time the window is read, so it should be 0, N, N x 2, N x 3 . . . for each window retrieved.
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter 1) Read [0xC757, 16 reg], Historical Log Header Block. Send: 0103 C757 0010 Command: -Register Address: 0xC757 -# Registers: 16 -----------------------------Receive: 010320 00000100 00000064 0012 0000 060717101511 060718101511 0000000000000000 Data: -Max Records: 0x100 = 256 records maximum. -Num Records: 0x64 = 100 records currently logged. -Record Size: 0x12 = 18 bytes per record. -Log Availability: 0x00 = 0, not in use, available for retrieval.
IQ 250/260 Meter -Register Address: -# Registers: Data: -Records per Window: -# of Repeats: -Window Status: -Record Index: -----------------------------Receive: Appendix B: IQ 250/260 Modbus Map 0xC350 3, 6 bytes 13. Since the window is 246 bytes, and the record is 18 bytes, 246\18 = 13.66, which means that 13 records evenly fit into a single window. This is 234 bytes, which means later on, we only need to read 234 bytes (117 registers) of the window to retrieve the records. 1.
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter If a record has all 0xFF for data, the timestamp is valid, and the index is NOT 0, then the record is legitimate. When the “filler” record is logged, its timestamp may not be “on the interval.” The next record taken will be on the next “proper interval,” adjusted to the hour. For example, if the interval is 1 minute, the first “real” record will be taken on the next minute (no seconds).
IQ 250/260 Meter Appendix B: IQ 250/260 Modbus Map index). In this example, this occurs when current index is 91 (the 8’th window). There are now 9 records available (100-91), so make Records per Window equal 9. 11) Repeat step 5 through 10. NOTES: Go back to step 5, where a couple of values have changed.
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter Log Record Interpretation The records of each log are composed of a 6 byte timestamp, and N data. The content of the data portion depends on the log. 1. System Event Record: Byte Value 0 1 2 3 4 5 timestamp 6 7 8 9 Group Event Mod Chan 10 11 12 13 Param1 Param2 Param3 Param4 Size: 14 bytes (20 bytes image). Data: The System Event data is 8 bytes; each byte is an enumerated value. Group: Group of the event.
Appendix B: IQ 250/260 Modbus Map IQ 250/260 Meter Group (Event group) Event (Event within group) Mod (Event modifier) Channel (1-4 for COMs, 7 for USER, 0 for FW) 0 1 0 slot# 0 0 1 2 3 log# log# log# 1-4 1-4 0-4 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF Log Activity Reset Log Retrieval Begin Log Retrieval End 1 2 3 0 0 0 1-4 0 0 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF Clock Activity Clock Changed Daylight Time On Daylight Time Off 1 2 3 0 0 sl
Appendix B: Modbus Mapping for IQ 250/260 o o o IQ 250/260 Meter Flash error counters are reset to zero in the unlikely event that both copies in EEPROM are corrupted. A “babbling log” is one that is saving records faster than the meter can handle long term. Onset of babbling occurs when a log fills a flash sector in less than an hour. For as long as babbling persists, a summary of records discarded is logged every 60 minutes.
Appendix B: IQ 250/260 Modbus Map IQ 250/260 Meter send: recv: :01 03 C7 57 00 10 - Historical Log status block :01 03 20 00 00 05 1E 00 00 05 1E 00 2C 00 00 06 08 17 51 08 00 06 08 18 4E 39 00 00 00 00 00 00 00 00 00 00 00 send: recv: :01 03 C3 4F 00 01 - Log Retrieval header :01 03 02 FF FF 00 00 send: recv: :01 10 C3 4F 00 04 08 02 80 05 01 00 00 00 00 - Engage the log :01 10 C3 4F 00 04 send: recv: :01 03 C7 57 00 10 - Historical Log status block :01 03 20 00 00 05 1E 00 00 05 1E 00 2C 00 02 06
Appendix B: Modbus Mapping for IQ 250/260 IQ 250/260 Meter b) Sample Historical Log Record: Historical Log Record and Programmable Settings 13|01|00 1F 42|1F 17 76|17 62 62 62 01|23 43 1F 77|18 34 34 75|23 44|06 67|18 34 44 76|23 0B 06 68|18 44 62 77|1F 0C|06 69|00 62 62 3F 0D 00 62 1F 40|1F 41 06 0E|17 75| . . . . . . 62 62 . . .
Appendix B: IQ 250/260 Modbus Map IQ 250/260 Meter Modbus Register Map (MM-1 to MM-32) The IQ 250/260 meter’s Modbus Register Map begins on the following page. www.eaton.
Appendix B: Modbus Mapping for IQ 250/260 B-24 IB02601006E IQ 250/260 Meter www.eaton.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments 03FB - 03FC 1020 - 1021 VARs, 3-Ph total FLOAT -9999 M to +9999 M VARs 2 03FD - 03FE 1022 - 1023 VAs, 3-Ph total FLOAT -9999 M to +9999 M VAs 2 03FF - 0400 1024 - 1025 Power Factor, 3-Ph total FLOAT -1.00 to +1.00 none 2 0401 - 0402 1026 - 1027 Frequency FLOAT 0 to 65.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments 1F5F - 1F60 8032 - 8033 Frequency, Minimum FLOAT 0 to 65.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal 1F9C 1F9D 1F9E - 1F9C 1F9D 1F9E 8093 - 8093 8094 - 8094 8095 - 8095 Description (Note 1) Format Unbalance, 0 sequence, Minimum Unbalance, -sequence, Minimum Current Unbalance, Minimum UINT16 UINT16 UINT16 Range (Note 6) 0 to 65535 0 to 65535 0 to 20000 Units or Resolution # Reg Comments 0.01% 0.01% 0.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments Expansions for Data and Control Block for Option Card 1 read-only except as indicated Data and Control Block -- Digital I/O Relay Card Overlay (Note 15) 2757 - 2757 10072 - 10072 Digital Input States UINT16 bit-mapped -------- 22221111 Two nibble fields: (2222) for input#2 and (1111) for input #1. Lsb in each nibble is the current state of the input.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments Data and Control Block -- Digital I/O Pulse Output Card Overlay (Note 15) read-only except as indicated 2757 - 2757 10072 - 10072 Digital Input States UINT16 bit-mapped dddd cccc bbbb aaaa Nibble "dddd" for input#4, "cccc" for input#3, "bbbb" for input#2 and "aaaa" for input#1.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments Data and Control Block -- Network Card Overlay (Note 15) read-only UINT16 bit-mapped rhp----- sfw-m-ii Flags: r=run mode; h=card is healthy; p=using last good known programmable settings Server flags: s=smtp ok; f=ftp ok; w=web server ok; m=modbus tcp/ip ok. IP Status ii: 00=IP not valid yet, 01=IP from p.
IQ 250/260 Meter App.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments Data and Control Block -- Digital I/O Pulse Output Card Overlay (Note 15) read-only except as indicated 2B3F - 2B3F 11072 - 11072 Digital Input States UINT16 bit-mapped dddd cccc bbbb aaaa Nibble "dddd" for input#4, "cccc" for input#3, "bbbb" for input#2 and "aaaa" for input#1.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments Data and Control Block -- Network Card Overlay (Note 15) read-only UINT16 bit-mapped rhp----- sfw-m-ii Flags: r=run mode; h=card is healthy; p=using last good known programmable settings Server flags: s=smtp ok; f=ftp ok; w=web server ok; m=modbus tcp/ip ok. IP Status ii: 00=IP not valid yet, 01=IP from p.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal 754D - 754D 30030 - 30030 Description (Note 1) Format Limit #1 In High Threshold SINT16 Range (Note 6) -200.0 to +200.0 Units or Resolution 0.1% of full scale # Reg Comments Threshold at which "above" limit clears; normally less than or equal to the "above" setpoint; see notes 11-12. Setpoint for the "below" limit (LM2), see notes 11-12. 1 754E - 754E 30031 - 30031 Limit #1 Out Low Setpoint SINT16 -200.0 to +200.0 0.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments For Class 10 unit c1=0.25A c2=0.5A c3=1A c4=5A 7633 - 7633 30260 - 30260 A phase CT compensation @ c1 (% error) SINT16 -15 to 15 0.01% 7634 - 7634 30261 - 30261 A phase CT compensation @ c2 (% error) SINT16 -15 to 15 0.01% 1 7635 - 7635 30262 - 30262 A phase CT compensation @ c3 (% error) SINT16 -15 to 15 0.
IQ 250/260 Meter App.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments 7D22 - 7D22 32035 - 32035 Relay Accumulators Scaling UINT16 bit-mapped -------- 22221111 The nibble informs what should be the scaling of the accumulator 0=no-scaling, 1=0.1, 2=0.01, 3= 1m, 4=0.1m, 5=0.01m, 6=1u, 7=0.1u; the value 15 disable the accumulator.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Settings Registers for Digital I/O Relay Card Units or Resolution First Overlay 80E8 - 80E8 33001 - 33001 Input#1 - 2 bindings & logging enables UINT16 bit-mapped -------- 2222 1111 # Reg Comments write only in PS update mode One nibble for each input. Assuming "abcc" as the bits in each nibble: "a": select this input for EOI (End Of Interval)pulse sensing.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Settings Registers for Digital I/O Pulse Output Card Units or Resolution # Reg Comments First Overlay write only in PS update mode 80E8 - 80E8 33001 - 33001 Input#1 - 4 bindings & logging enables UINT16 bit-mapped 44443333 22221111 One nibble for each input. Assuming "abcc" as the bits in each nibble: "a": select this input for EOI (End Of Interval)pulse sensing.
IQ 250/260 Meter App.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Settings Registers for Analog Out 0-1mA / Analog Out 4-20mA Cards Units or Resolution # Reg Comments Second Overlay write only in PS update mode 8127 - 8127 33064 - 33064 Update rate UINT16 0 to 65535 Fixed -- see specifications.
IQ 250/260 Meter App. B: Modbus Map Modbus Address Hex Decimal Description (Note 1) Format Range (Note 6) Units or Resolution # Reg Comments Second Overlay write only in PS update mode 8127 - 8127 33064 - 33064 General Options bit-mapped -------- ---s cwme Servers enable(1) or disable(0) flags: s=Modbus_TCP_server; c=Modbus_TCP_client; w=Web server ; m=HTTP Modbus RTU for diagnostics. Sleep enabled e=0; sleep disabled e=1.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App.
IQ 250/260 Meter App. B: Modbus Map Data Formats ASCII ASCII characters packed 2 per register in high, low order and without any termination characters. SINT16 / UINT16 16-bit signed / unsigned integer. SINT32 / UINT32 32-bit signed / unsigned integer spanning 2 registers. The lower-addressed register is the high order half. FLOAT 32-bit IEEE floating point number spanning 2 registers. The lower-addressed register is the high order half (i.e., contains the exponent).
IQ 250/260 Meter App. B: Modbus Map 19 Depending on the meter model, there are 15, 29, or 45 flash sectors available in a common pool for distribution among the historical and waveform logs. The pool size, number of sectors for each log, and the number of registers per record together determine the maximum number of records a log can hold.
Appendix C: IQ 250/260 Meter Using DNP Mapping for IQ 250/260 App.C Using DNP Mapping for IQ 250/260 Overview This Appendix describes the functionality of the IQ 250/260 meter's version of the DNP protocol. A DNP programmer needs this information to retrieve data from the meter. The DNP version used by the IQ 250/260 is a reduced set of the Distributed Network Protocol Version 3.0 subset 2; it gives enough functionality to get critical measurements from the meter.
Appendix C: Using DNP Mapping for IQ 250/260 IQ 250/260 Meter Application Layer The IQ 250/260 meter’s DNP version supports the Read function, Write Function, the Direct Operate function and the Direct Operate Unconfirmed function. The Read function (code 01) provides a means for reading the critical measurement data from the IQ 250/260 meter. This function should be posted to read object 60 variation 1, which will read all the available Class 0 objects from the DNP register map.
Appendix C: IQ 250/260 Meter Using DNP Mapping for IQ 250/260 DNP Register Map Object 10 – Binary Output States Object Point Var Format Range Multiplier Units Comments 10 0 2 Description Reset Counters Energy BYTE Always 1 N/A None Read by Class 0 or with qualifier 0, 1, 2 or 6 10 1 2 Change to Modbus RTU Protocol BYTE Always 1 N/A None Read by Class 0 or with qualifier 0, 1, 2 or 6 10 2 2 Reset Demand Cntrs (Max / Min ) BYTE Always 1 N/A None Read by Class 0 or with qual
Appendix C: Using DNP Mapping for IQ 250/260 IQ 250/260 Meter Object 30 – Analog Inputs (Secondary Readings) - Read via Class 0 or with qualifier 0, 1, 2, or 6 Object Point Var Description Format Range Multiplier Units Comments 30 30 0 1 4 4 Meter Health Volts A-N sint16 sint16 0 or 1 0 to 32767 N/A (150 / 32768) None V 0 = OK Values above 150V secondary read 32767.
Appendix C: IQ 250/260 Meter Using DNP Mapping for IQ 250/260 Object 80 – Internal Indicator Object Point Var 80 0 1 Description Format Range Multiplier Units Comments Device Restart Bit N/A N/A N/A none Clear via Function 2 (Write), Qualifier Code 0. DNP Message Layouts Legend All numbers are in hexadecimal base. In addition the following symbols are used.
Appendix C: Using DNP Mapping for IQ 250/260 IQ 250/260 Meter Link Status Request 05 64 05 C9 dst src crc Reply 05 64 05 0B src dst crc src crc Application Layer related frames Clear Restart Request 05 64 0E C4 Cx Cy 02 50 05 64 0A 44 Cx Cy 81 int. ind. 05 64 0B C4 Cx Cy 01 3C Request 05 64 14 C4 (alternate) Cx Cy 01 3C Reply 05 64 72 44 (same for either request) Cx Cy 81 int. ind.
Appendix C: IQ 250/260 Meter Using DNP Mapping for IQ 250/260 Reset Energy Request 05 64 18 C4 Cx Cy 05 0C 00 00 00 05 64 1A 44 Cx Cy 81 int. ind. 01 00 00 00 Request 05 64 1A C4 (alternate) Cx Cy 05 0C 01 01 00 00 00 00 05 64 1C 44 Cx Cy 81 int. ind.
Appendix C: Using DNP Mapping for IQ 250/260 IQ 250/260 Meter Request 05 64 1A C4 (alternate) Cx Cy 05 0C 01 01 00 00 00 00 05 64 1C 44 Cx Cy 81 int. ind. 0C 01 00 00 01 00 00 00 05 64 0A 44 Cx Cy 81 int. ind. Reply dst src 28 01 crc 02 00 00 03 00 00 00 00 00 crc 02 00 00 03 00 00 00 crc crc src 00 dst crc 28 01 crc Error Reply Reply src dst crc crc Internal Indication Bits Bits implemented in the IQ 250/260 meter are listed below.