Installation Manual

Table Of Contents
IQ 250/260 Meter App. B: Modbus Map
www.eaton.com IB02601006E MM-6
Description (Note 1) Format Range (Note 6) Units or Resolution Comments
Modbus Address
Hex Decimal
#
Reg
0BBF - 0BC0 3008 - 3009 Watts, Phase A FLOAT -9999 M to +9999 M watts 2
0BC1 - 0BC2 3010 - 3011 Watts, Phase B FLOAT -9999 M to +9999 M watts 2
0BC3 - 0BC4 3012 - 3013 Watts, Phase C FLOAT -9999 M to +9999 M watts 2
0BC5 - 0BC6 3014 - 3015 VARs, Phase A FLOAT -9999 M to +9999 M VARs 2
OBC7 - 0BC8 3016 - 3017 VARs, Phase B FLOAT -9999 M to +9999 M VARs 2
0BC9 - 0BCA 3018 - 3019 VARs, Phase C FLOAT -9999 M to +9999 M VARs 2
0BCB - 0BCC 3020 - 3021 VAs, Phase A FLOAT -9999 M to +9999 M VAs 2
0BCD - 0BCE 3022 - 3023 VAs, Phase B FLOAT -9999 M to +9999 M VAs 2
0BCF - 0BD0 3024 - 3025 VAs, Phase C FLOAT -9999 M to +9999 M VAs 2
0BD1 - 0BD2 3026 - 3027 Power Factor, Phase A FLOAT -1.00 to +1.00 none 2
0BD3 - 0BD4 3028 - 3029 Power Factor, Phase B FLOAT -1.00 to +1.00 none 2
0BD5 - 0BD6 3030 - 3031 Power Factor, Phase C FLOAT -1.00 to +1.00 none 2
0BD7 - 0BD8 3032 - 3033 W-hours, Received SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BD9 - 0BDA 3034 - 3035 W-hours, Delivered SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BDB - 0BDC 3036 - 3037 W-hours, Net SINT32 -99999999 to 99999999 Wh per energy format 2
0BDD - 0BDE 3038 - 3039 W-hours, Total SINT32 0 to 99999999 Wh per energy format 2
0BDF - 0BE0 3040 - 3041 VAR-hours, Positive SINT32 0 to 99999999 VARh per energy format 2
0BE1 - 0BE2 3042 - 3043 VAR-hours, Negative SINT32 0 to -99999999 VARh per energy format 2
0BE3 - 0BE4 3044 - 3045 VAR-hours, Net SINT32 -99999999 to 99999999 VARh per energy format 2
0BE5 - 0BE6 3046 - 3047 VAR-hours, Total SINT32 0 to 99999999 VARh per energy format 2
0BE7 - 0BE8 3048 - 3049 VA-hours, Total SINT32 0 to 99999999 VAh per energy format 2
0BE9 - 0BEA 3050 - 3051 W-hours, Received, Phase A SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BEB - 0BEC 3052 - 3053 W-hours, Received, Phase B SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BED - 0BEE 3054 - 3055 W-hours, Received, Phase C SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BEF - 0BF0 3056 - 3057 W-hours, Delivered, Phase A SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BF1 - 0BF2 3058 - 3059 W-hours, Delivered, Phase B SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BF3 - 0BF4 3060 - 3061 W-hours, Delivered, Phase C SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BF5 - 0BF6 3062 - 3063 W-hours, Net, Phase A SINT32 -99999999 to 99999999 Wh per energy format 2
Per phase power and PF have values
only for WYE hookup and will be
zero for all other hookups.
* Wh received & delivered always have opposite signs
* Wh received is positive for "view as load", delivered is
positive for "view as generator"
* 5 to 8 digits
* decimal point implied, per energy format
* resolution of digit before decimal point = units, kilo, or
mega, per energy format
* see note 10