IQ 250/260 Meter App. B: Modbus Map
www.eaton.com IB02601006E MM-23
Description (Note 1) Format Range (Note 6) Units or Resolution Comments
Modbus Address
Hex Decimal
#
Reg
read-only
2B3F - 2B3F 11072 - 11072 Card and Network Status UINT16 bit-mapped
rhp----- sfw-m-ii
Flags: r=run mode; h=card is healthy; p=using last good
known programmable settings
Server flags: s=smtp ok; f=ftp ok; w=web server ok;
m=modbus tcp/ip ok.
IP Status ii: 00=IP not valid yet, 01=IP from p.settings;
10=IP from DHCP;11=using last good known IP.
1
2B40 - 2B40 11073 - 11073 Reserved Reserved 1
2B41 - 2B43 11074 - 11076 MAC address in use by the network card UINT16 bit-mapped 6 bytes These 3 registers hold the 6 bytes of the card's Ethernet
MAC address.
3
2B44 - 2B47 11077 - 11080 Current IP Address UINT16 These 4 registers hold the 4 numbers (1 number each
register) that make the IP address used by the card.
4
2B48 - 2B48 11081 - 11081 Current IP Mask Length UINT16 0 to 32 Number of bits that are set in the IP address mask,
starting from the Msb of the 32 bit word.
Example 24 = 255.255.255.0; a value of 2 would mean
192.0.0.0
1
2B49 - 2B4A 11082 - 11083 Firmware Version ASCII 4 char none Version of the BOOT firmware of the card, left justified
and padded with spaces. Blank for boards without
embedded firmware.
2
2B4B - 2B4C 11084 - 11085 Firmware Version ASCII 4 char none Version of the RUN firmware of the card, left justified and
padded with spaces. Blank for boards without embedded
firmware.
2
2B4D - 2B78 11086 - 11129 Reserved Reserved for Extended Nw Status 44
Block Size: 58
read-only
2EDF - 2EE0 12000 - 12001 Option Card 1, Input 1 Accumulator UINT32 0 to 999999999 number of transitions 2
2EE1 - 2EE6 12002 - 12007 Option Card 1, Inputs 2-4 Accumulators UINT32 0 to 999999999 number of transitions 6
2EE7 - 2EE8 12008 - 12009 Option Card 1, Output or Relay 1 Accumulator UINT32 0 to 999999999 number of transitions 2
2EE9 - 2EEE 12010 - 12015 Option Card 1, Output or Relays 2-4 UINT32 0 to 999999999 number of transitions 6
2EEF - 2EF6 12016 - 12023 Option Card 2 Inputs Accumulators UINT32 0 to 999999999 number of transitions 8
2EF7 - 2EFE 12024 - 12031 Option Card 2 Outputs Accumulators UINT32 0 to 999999999 number of transitions 8
Block Size: 32
Data and Control Block -- Network Card Overlay (Note 15)
Accumulators Block
These are unscaled counts. See option card section
for scaled versions.
Input accumulators count either or both transitions;
output accumulators count both transitions.
Unused accumulators always read 0.