Datasheet

10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Sensors (EG000026) / End switch (EC000030)
Electric engineering, automation, process control engineering / Binary sensor technology, safety-related sensor technology / Position switch / Position switch (Type 1)
(ecl@ss10.0.1-27-27-06-01 [AGZ382015])
Width sensor mm 31
Diameter sensor mm 0
Height of sensor mm 61
Length of sensor mm 33.5
Rated operation current Ie at AC-15, 24 V A 6
Rated operation current Ie at AC-15, 125 V A 6
Rated operation current Ie at AC-15, 230 V A 6
Rated operation current Ie at DC-13, 24 V A 3
Rated operation current Ie at DC-13, 125 V A 0.8
Rated operation current Ie at DC-13, 230 V A 0.3
Switching function Slow-action switch
Switching function latching No
Output electronic No
Forced opening Yes
Number of safety auxiliary contacts 0
Number of contacts as normally closed contact 1
Number of contacts as normally open contact 1
Number of contacts as change-over contact 0
Type of interface None
Type of interface for safety communication None
Construction type housing Cuboid
Material housing Metal
Coating housing Other
Type of control element Rotary lever
Alignment of the control element Other
Type of electric connection Cable entry metrical
With status indication No
Suitable for safety functions Yes
Explosion safety category for gas None
Explosion safety category for dust None
Ambient temperature during operating °C 25 - 70
02/07/2019 Eaton 266146 ED2019 V52.0 EN 3 / 5