Pushbuttons and Indicating Lights
30.5 mm Heavy-Duty Watertight/Oiltight10250T
Electrical Ratings
Electrical Ratings—Contact Block
Description Specification
Insulation U
i
= 660 Vac or Vdc
Thermal I
th
= 10A
Short Circuit Coordination to IEC/EN 60947-5-1
Rated conditional short circuit current 1 kA
Fuse type GE power controls TIA 10, red spot type gG, 10A, 660 Vac, 460 Vdc, BS88-2,
IEC 60269-2-1
UL rating A600, P600
AC load life duty cycle 1200 operations/hour
10A 110V pf 0.4—1 x 10
6
operations
5A 250V pf 0.4—1 x 10
6
operations
2A 600V pf 0.4—1 x 10
6
operations
Switching capacity
AC 15 rated make/break (11 x l
e
at 1.1 x U
e
)
6A 120V pf 0.3
4A 240V pf 0.3
2A 660V pf 0.3
DC13 rated make/break (1.1 x l
e
at 1.1 x U
e
)
1.0A 125V L/R
>
0.95 at 300 ms
0.55A 250V L/R
>
0.95 at 300 ms
0.1A 660V L/R
>
0.95 at 300 ms
10A 110V pure resistive
Maximum ratings for logic level and
hostile atmosphere application
Maximum amperes 0.5A
Maximum volts 120 Vac/Vdc
Description
50 Vac or 60 Hz Vdc
120 240 480 600 24/28 125 250
Meet or Exceed NEMA Rating Designations A600, A300 and B300 for AC and P600 for DC
Make and emerg. interrupting capacity (amp) 60 30 15 12 5.7 1.1 0.55
Normal load break (amp) 6 3 1.5 1.2 5.7 1.1 0.55
Thermal current (amp) 101010105.05.05.0
Voltamperes:
Make and emerg. interrupting capacity 7200 7200 7200 7200 138 138 138
Normal load break 720 720 720 720 138 138 138