Pushbuttons and Indicating Lights
30.5 mm Class I Division 2 Hazardous Locations—10250T/E34
Electrical Ratings—Contact Block
Temperature Codes
All illuminated devices have operating temperatures below
100°C except for the following catalog numbers with
temperature codes per NEC table 500.5(d) and UL 1604:
Note: For additional technical information, see Publication Number
TD.7.4.T.E.04.
Meet or Exceed NEMA Contact Rating Designations A600 and Q300
Description
A600 (AC) Q300 (DC)
120V 240V 480V 600V 125V 250V
Make and emerg. interrupting capacity (amps) 60 30 15 12 0.55 0.27
Normal load break (amps) 6 3 1.5 1.2 0.55 0.27
Thermal current (amps) 10 10 10 10 2.5 2.5
Voltamperes:
Maximum make 7200 7200 7200 7200 69 69
Maximum break 720 720 720 720 69 69
10250T E34 Temp. Code
10250T201H E34RB120H T3C
10250T202H E34RB240H T3A
10250T471H E34SB120H TC3
10250T472H E34SB240H T3B
10250T80H T3C
10250T81H T3B
All selector switches w/120 MB lamp T3C
All illuminated devices with lamp 1835 T4A