Cut Sheet

Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—June 2015 www.eaton.com V7-T1-43
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.4
Pushbuttons and Indicating Lights
16.2 mm Pushbuttons—RMQ-16
Technical Data and Specifications
RMQ-16
Specification
Illuminated Pushbutton
Operators (Maintained)
Illuminated Selector
SwitchesDescription Unit Contact Elements Indicating Lights
General Technical Data
Standards UL, CSA, IEC/EN 60 947, VDE 0660, CE
Lifespan, mechanical (operations) x 10
5
100 30 (3) 3
Maximum operating frequency Ops/h 3600 3600 (1800) 1800
Operating force N 3 4
Operating torque Nm 0.2
Degree of protection to IEC/EN 60 529 IP20 with ISH2,8 IP65 IP65 IP65
Climatic proofing Damp heat, constant, to IEC 60 068-2-3/Damp heat, cyclical, to IEC 60 068-2-30
Ambient temperature
Open °C –25 to 60 –25 to 60 –25 to 60 –25 to 60
Enclosed °C –25 to 40 –25 to 40 –25 to 40 –25 to 40
Mounting position As required As required As required As required
Mechanical shock resistance to IEC 60 068-2-27
(half-sinusoidal shock, duration 11 ms)
g40404040
Terminal capacity (min./max.) mm
2
0.5/1.0 0.5/1.0 0.5/1.0 0.5/1.0
Blade terminal 2.8 mm x 0.8 mm to DIN 46 244
Ferrule 2.8 mm x 0.8 mm to DIN 46 247 and IEC 60 760
Dimensions See Page V7-T1-45 See Page V7-T1-45 See Page V7-T1-45 See Page V7-T1-45
Contacts
Rated impulse withstand voltage U
imp
V 4000 800 800 800
Rated insulation voltage U
i
V 250 250 250 250
Overvoltage category/pollution degree III/3 III/3 III/3 III/3
Rated operational voltage U
e
(max.) V 250 24 24 24
Rated operational current I
e
(max.) A 4
Control circuit reliability at
24 Vdc/5 mA (Fault probability Hr) <10
–7
, <1 fault in 10
7
operations
5 Vdc/1 mA (Fault probability Hr) <5 x 10
–6
, < fault in 5 x 10
6
operations
Use of insulated ferrule ISH 2.8
From U
e
>24 Vac/dc recommended >24 Vac/dc recommended >24 Vac/dc recommended >24 Vac/dc recommended
From U
e
>50 Vac or 120 Vdc is mandatory, even on unused blade terminals
Maximum short-circuit protective device
Fuseless Type FAZ-B6
Fuse A gG/gL 10
Switching Capacity
Rated operational current I
e
AC-15
24V A 4
48V A 4
110V A 4
230V A 4
DC-13
24V A 3
42V A 1.0
60V A 0.8
110V A 0.5
220V A 0.2
UL/CSA Data UL listed File No. E 29 184, Guide No. NKCR/CSA certified File No. 46 552 Class No. 321103
Blade terminal 0.110 x 0.032 in 0.110 x 0.032 in 0.110 x 0.032 in 0.110 x 0.032 in
Fast-on connector 0.110 x 0.032 in AMP #60 197-1, 62 050-1 or equivalent
Rated voltage maximum AC Vac 300 24 24 24
Contact rating code AC E10/E01 C300/Q300
Thermal continuous test current A 2.5
Rated voltage maximum DC Vdc 300
Contact rating code DC E10/E01 C300/R300
Thermal continuous test current A 2.5