Cut Sheet

Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—July 2015 www.eaton.com V7-T3-181
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3.8
Control Relays and Timers
Ti m i n g Rel ay s
Technical Data and Specifications
TMR5 Time Delay Relays
Description Specification
Voltage tolerance
AC operation +10/–15% of nominal at 50/60 Hz
DC operation +10/–15% of nominal
Load burden 2 VA
Setting accuracy
Maximum setting (adjustable) +5%, –0%
Minimum setting (adjustable) +0%, –50%
Fixed time delay
< 2 seconds +1%
0.1–2 seconds ±5%
Repeat accuracy (constant voltage and temperature)
> 2 seconds delay ±0.1%
0.1–2 seconds delay ±2%
Reset time
ON Delay/interval/repeat cycle 0.1 second
OFF Delay/single shot/watchdog 0.04 second
Startup time (time from when power is applied until unit is timing)
120 and 240 V units 0.05 second
12, 24 and 48 V units 0.08 second
Maintain function time (time unit
continues to time after power is
removed)
0.01 second
Temperature
12–120 V input voltage –18 to 150 °F (–28 to 65 °C)
240 V input voltage –18 to 122 °F (–28 to 50 °C)
Insulation voltage 2000 V
Output contacts DPDT 10 A @ 240 Vac/30 Vdc,
1/2 hp @ 120/240 Vac (NO contacts)
1/3 hp @ 120/240 Vac (NC contacts)
B300 and R300; AC-15 and DC-13
Life
Mechanical 10,000,000 operations
Full load 100,000 operations
Wiring Diagrams
Wiring for 8-Pin Units Wiring for 11-Pin Control
Switch Trigger Units
Wiring for 11-Pin Power
Tri g g e r U n i t s
1
(DC)+
L1
−(DC)
L2
8
Input Voltage
4
36
27
5
1
(DC)+
L1
(DC)−
L2
11
Input Voltage
Control
Switch
48
39
6
210
75
1
(DC)+
L1
(DC)−
L2
+
11
Input Voltage
* Should Be Same Voltage
as Input Voltage
Power
Trigger *
48
39
6
210
75