3.8
Control Relays and Timers
Ti m i ng Relay s
Product Selection
TMRP Timing Relays
Technical Data and Specifications
TMRP Timing Relays
Note
1
Refer to Function Code Cross-Reference Guide on Page V7-T3-167 for function details.
Supply Voltage Description
Catalog
Number
10-Function
12–240 Vac/Vdc Control switch trigger, DPDT TMRP5100
Control switch trigger, SPDT TMRP5101
Power trigger, DPDT TMRP5102
TMRP5100
Description TMRP5100 TMRP5101 TMRP5102
Functions
1
A, B, C, D, E, F, G, H, I, J A, B, C, D, E, F, G, H, I, J A, B, C
Time range 0.1 sec to 9,990 hours 0.1 sec to 9,990 hours 0.1 sec to 9,990 hours
Input
Supply voltage 12–240 Vac/Vdc 12–240 Vac/Vdc 12–240 Vac/Vdc
Supply voltage tolerance ±15% ±15% ±15%
Rated consumption 2.5 VA (2 W) maximum 2.5 VA (2 W) maximum 2.5 VA (2 W) maximum
Reset time 150 ms 150 ms 150 ms
Reverse polarity protection Yes Yes Yes
Operate time 25 ms maximum 25 ms maximum 25 ms maximum
Release time 25 ms maximum 25 ms maximum 25 ms maximum
Rated surge voltage 4 kV 4 kV 4 kV
Output
Contact configuration DPDT SPDT DPDT
Contact rating (AC) 12 A resistive at 120, 240 UL 508 12 A resistive at 120, 240 UL 508 12 A resistive at 120, 240 UL 508
Contact rating (DC) 12 A resistive at 30 UL 508 12 A resistive at 30 UL 508 12 A resistive at 30 UL 508
Contact rating horsepower 1/2 at 120 Vac, 1 at 240 Vac 1/2 at 120 Vac, 1 at 240 Vac 1/2 at 120 Vac, 1 at 240 Vac
Contact rating pilot duty A300, 720 VA at 240 Vac A300, 720 VA at 240 Vac A300, 720 VA at 240 Vac
Minimum load 12 V/100 mA 12 V/100 mA 12 V/100 mA
Contact material Silver-nickel 90/10 Silver-nickel 90/10 Silver-nickel 90/10
Contact resistance 100 milliohms max. at 1 A 12 Vdc 100 milliohms max. at 1 A 12 Vdc 100 milliohms max. at 1 A 12 Vdc
Mechanical life—full load 10 million operations 10 million operations 10 million operations
Electrical life—full load 100,000 operations 100,000 operations 100,000 operations
Control Signal
Minimum control pulse length 50 ms minimum 50 ms minimum 50 ms minimum
Accuracy
Repetition accuracy 0.10% at constant voltage and temperature 0.10% at constant voltage and temperature 0.10% at constant voltage and temperature
Physical
Ambient temperature –10 to 55 °C –10 to 55 °C –10 to 55 °C
Storage temperature –40 to 85 °C –40 to 85 °C –40 to 85 °C
Mounting Use with D3PA3 socket Use with D3PA2 socket Use with D3PA2 socket