Cut Sheet

Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T4-45
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4.2
PLC, I/O and Communications Products
XC Series Programmable Logic Controllers
XIOC Analog Modules
XIOC Thermocouple Module
Description Unit XIOC-8AI-I2 XIOC-8AI-U1 XIOC-8AI-U2 XIOC-4T-PT
Modules
Input voltage Vdc 0 to 10 –10 to +10
Input current mA 4–20
Resolution, digital bit 12 12 12 15 bit with sign
Conversion time
<
5 ms
<
5 ms
<
5 ms
Total errors %
<
± 1 (of full-scale value)
<
± 1 (of full-scale value)
<
± 1 (of full-scale value)
<
± 1 (of full-scale value)
Input resistance kohm 100 100
Potential isolation
Circuit within each channel With optocouplers With optocouplers With optocouplers With optocouplers
Between the input channels No No No No
Input channels Number 8 8 8 4
Terminals Plug-in terminal block Plug-in terminal block Plug-in terminal block Plug-in terminal block
External power supply 24 Vdc (–15 to +20%),
approx. 150 mA
24 Vdc (–15 to +20%),
approx. 150 mA
24 Vdc (–15 to +20%),
approx. 150 mA
24 Vdc (–15 to +20%),
100 mA
External resistance (R) kohm Max. 0.4, 4 channels
Connection type 2-core shielded cable (
<
20m) 2-core shielded cable (
<
20m) 2-core shielded cable (
<
20m) Shielded cable
Platinum RTD PT100 (IEC 751), PT1000
Accuracy
–20° to 40°C (PT100) °C ±0.5
–50° to 400°C (PT100) °C ±3
–50° to 400°C (PT1000) °C ±6
Temperature measuring range –20 to 40°/–50 to 400°
(uninterrupted current: 2 mA)
Internal current consumption (5 Vdc) mA Normally 100 Normally 100 Normally 100 Max. 200
Additional function Linearization
Fault detection
–20° to 40°C
——
<
–25°C or
>
+45°C = resistance
value 7FFFFhex
–50° to 400°C
<
–60°C or
>
+410°C =
resistance value 7FFFFhex
Response to cable break or unused inputs In these cases, the resistance
value is 7FFFhex
Weight kg 0.18 0.18 0.18 0.18
Description Unit XIOC-4AI-T
Channels
Number 4
Temperature measuring range °C Type K: –270 to 1370
Type J: –210 to 1200
Type B: 100 to 1800
Type N: –270 to 1300
Type E: –270 to 1000
Type R: –50 to 1760
Type T: –200 to 400
Voltage measurement mV –50 to 50
–100 to 100
–500 to 500
–1000 to 1000
Cold-junction compensation Yes, built-in
Interference suppression 50 Hz, 60 Hz
Unit 0.1°C, 0.1 F
Resolution bit 16
Total errors % ±0.5 of measurement range
Conversion time <1s
Temperature coefficient <200 ppm/°C of measurement range